BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M286259
Premises: 16 EAST 52 STREET MANHATTAN BIN: 1035475     Block: 1287   Lot: 58
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 16 E 52 ST Census Tract:   102 Health Area:  4800
SUITE 502 Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   MAXWELL MEDICAL
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/23/2008 2:55 PM
Application Entered:   10/23/2008 Job Start Date:   10/23/2008
Last Change:   08/22/2025 Job End Date:   11/24/2008
Appointment Status:   
Last Inspection By:   REDDINGTON, J.       On     12/01/2008      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011929 Licensee Name: RICHARD MORALES
Firm: 003567 Firm Name: K & M ELECTRICAL CONTNG I
Firm Phone: 212-675-3486  Firm Address: 132 WEST 31ST STREET, LL NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $198.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOANNE AGOGLIA
Owner Business Name: TRIGON 52 LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  502  45  20  44  28  65             
Buildings Total 45  20  44  28  65                
Total Units : 202 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/05/2008
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M286259
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/01/2008 12/05/2008 SR2 A (45) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: M286259
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
PANTRY: NO G.F.I.PROTECTION IN OFFICE PANTRY (SINK) COUNTER AREA
OPEN 12/01/2008 12/01/2008
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
E.CLOSET: 1 1/4" KO SEAL MISSING TROUGH
OPEN 12/01/2008 12/01/2008
 
003 (999) OTHER
E.CLOSET: ART.511 - NO MC ACBLE (AS A MINIMUM METALLIC RACEWAY WIR-ING METHOD) PROVIDED FOR LIGHTS IN PATIENT ROOMS IN A MEDICAL FACIL
OPEN 12/01/2008 12/01/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.