Electrical Application Details for App #: M285240
Premises: 14 ST MARKS PLACE MANHATTAN BIN: 1006666     Block: 463   Lot: 16
   

DOB NOW: Inspections


Filed: 14 ST MARKS PL Census Tract:   38 Health Area:  6500
BSMT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   09/23/2008 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     09/23/2008      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: AFRICAN AMERICAN SM.PROP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/23/2008
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 09/23/2008
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M285240
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/23/2008 09/23/2008 SVJ W (1) (9)
INSPECTION COMMENTS: *RE: M122605 - CERTIFIED LETTER SENT TO OWNER* SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: M285240
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
1/FOR 100 AMP SER 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUITS WIRINH THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE EQUIPMENT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUITS WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NOT INSTALLED 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUIT WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
004 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
4FL BATHROOM AND BSMT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS ANDBRANCH CIRCUITS WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
005 ( 17) DEFECTIVE SWITCHES ARE IN USE
BSMT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCH CIRCUITSWIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
006 ( 26) ARMORED CABLES ARE INSTALLED EXPOSED
BSMT THROUGH-OUT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUITS WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCH CIRCUITSWIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
008 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL IN BSMT 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUITS WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008
 
009 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
2/SER AND PANEL 8 WIRE FUSED AT 100 AMP.1/PANEL FEEDERS AND BRANCHCIRCUITS WIRING THROUGH-OUT
OPEN 09/23/2008 09/23/2008