BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M284748
Premises: 91 ORCHARD STREET MANHATTAN BIN: 1079706     Block: 414   Lot: 59
   
Application Completed and Certified

Filed: 91 ORCHARD ST Census Tract:   18 Health Area:  7400
SIDEWALK Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   BROOME STREET,    DELANCEY STREET
Status:   C - JOB IS SIGNED OFF 08/22/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/10/2008 9:36 AM
Application Entered:   09/10/2008 Job Start Date:   09/10/2008
Last Change:   08/22/2012 Job End Date:   09/10/2009
Appointment Status:   
Last Inspection By:   ARTAN, MUJKO       On     06/30/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010285 Licensee Name: GREGORY PAPANTONIOU
Firm: 003867 Firm Name: BOROWIDE ELECT'L CONTR'S
Firm Phone: 718-204-1347  Firm Address: 36-07 20TH AVENUE INC ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
2 - TEMPORARY CONSTRUCTION
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ROCKLEDGE SCAFFOLDING
Authorized Representative:  MARY MURPHY
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                       
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/24/2008
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TEMPORARY SHED LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M284748
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/08/2008 11/13/2008 DAH J (15) (0)
INSPECTION COMMENTS: NONE
 
(2) 11/18/2008 11/24/2008 CCH A (30) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 06/30/2012 07/24/2012 AMJ C R (5) (0) Y
INSPECTION COMMENTS: NO SIDEWALK SHED ON PREMISES

OBJECTION FOR APPLICATION #: M284748
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A) SHED: RACEWAY IS NOT PROPERLY SUPPORTED358.30A
RSLV 11/18/2008 11/18/2008 06/30/2012
 
002 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
SHED: FIXTURE NOT PROPERLY SUPPORTED
RSLV 11/18/2008 11/18/2008 06/30/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back