| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
4 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL MORE THAN 6 SER IN THE BUILDING |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED OPEN 119 BOXES THRU OUT BSMT |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 003 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED THRU OUT BSMT |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 004 |
( 26) |
ARMORED CABLES ARE INSTALLED EXPOSED THRU OUT BSMT |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 005 |
( 27) |
ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS THRU OUT BSMT |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE THRU OUT THE BSMT, NOT A FINAL INSPECTION SEE M270502 |
RSLV |
06/03/2008 |
06/03/2008 |
03/05/2009 |
| |
| 007 |
(999) |
OTHER BSMT: SERVICE END COND RAN IN PARALELL NOT THE SAME310.4 |
RSLV |
03/05/2009 |
03/05/2009 |
10/22/2009 |
| |
| 008 |
(999) |
OTHER BSMT: SERVICE COPPER DETAIL BOX LINE AND LOAD SAME RACEWAY230.7 |
RSLV |
03/05/2009 |
03/05/2009 |
10/22/2009 |
| |
| 009 |
(999) |
OTHER BSMT: SUPPLEMENTAL AND RACEWAY NOT CONTINUOUS250 |
RSLV |
03/05/2009 |
03/05/2009 |
10/22/2009 |
| |
| 010 |
(999) |
OTHER BSMT: SERVICE SW FUSES OVER 601 AMP NOT CO-ORDINATE EITH 2ND FUSE240.12 |
RSLV |
03/05/2009 |
03/05/2009 |
10/22/2009 |