| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
1 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
70 |
|
| B. Over #2 to 1/0 |
4 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
18 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
72 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
8 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: NOT AS PER ADVISORY DRAWING 487334 STES CONED/8 SETS DRAWING |
RSLV |
11/01/2010 |
11/01/2010 |
08/13/2012 |
| |
| 002 |
(999) |
OTHER BSMT: FIRE SW NOT RED 1200 AMP...... - 695.4B4 |
RSLV |
11/01/2010 |
11/01/2010 |
08/13/2012 |
| |
| 003 |
(999) |
OTHER BSMT: MB2 COLOR CODE (NOT FILED FOR).... - 210.4D 210.5 |
RSLV |
11/01/2010 |
11/01/2010 |
08/13/2012 |
| |
| 004 |
(999) |
OTHER BSMT FIRE PUMP SERVICE SW IS NOT REMOTE 12 INCHES APART FROM EQUIP-MENT ART 695.4B3 |
RSLV |
08/13/2012 |
08/13/2012 |
01/14/2013 |
| |
| 005 |
(999) |
OTHER BSMT RACE WAY OUTSIDE OF SERVICE AND CONTROL ROOM IS NOT ENCASE IN2IN OF CONCRETE ART 695.6B |
RSLV |
08/13/2012 |
01/14/2013 |
01/31/2013 |
| |
| 006 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX 18TH FLR PNL/TRIM |
RSLV |
08/13/2012 |
01/14/2013 |
01/31/2013 |
| |
| 007 |
(999) |
OTHER ALL FLRS ALL AREA WITH MC CABLE-BRANCH CIRCUIT WIRING OUTLET BOXES AAS PER ARTICLE 250.146 |
RSLV |
08/13/2012 |
01/14/2013 |
01/31/2013 |
| |
| 008 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED 17FL: VERTICAL CABLE SUPPORT OF PROPER SIZE,17,14,9,5 FLOORS |
RSLV |
01/14/2013 |
01/14/2013 |
01/31/2013 |
| |
| 009 |
(999) |
OTHER BSMT FIRE PUMP SERVICE SW IS NOT REMOTE 12" APART FROM EQUIPMENT- ART.695.4B3 |
RSLV |
01/14/2013 |
01/14/2013 |
01/31/2013 |