BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M275789
Premises: 49 EAST 34 STREET MANHATTAN BIN: 1017101     Block: 864   Lot: 28
   

DOB NOW: Inspections


Filed: 47 E 34 ST Census Tract:   74 Health Area:  5200
LEXINGTON AVENUE Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   106
Related Job Number:    104339930
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   C - SIGNOFF IS AWAITING FEE PAYMENT 06/11/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/08/2008 10:18 AM
Application Entered:   01/08/2008 Job Start Date:   02/01/2008
Last Change:   06/11/2024 Job End Date:   02/01/2009
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     06/11/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011359 Licensee Name: JAMES J ACCARDI
Firm: 003338 Firm Name: JUNE ELECTRIC CORP.
Firm Phone: 718-597-3937  Firm Address: 3110 WILKINSON AVENUE-SUITE 2C BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup: JOHN MCADAMS
Owner Business Name: TIME SQUARE CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  2-800AMP, 1-1200AMP
E. Over 1200 AMPS  3  1-2500AMP, 2-3000AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  11  11-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  110  110-1 PHASE 24 CIRCUIT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  8-225AMPS 42CIRCUIT PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 2798  3416  330  1104  2798     340           
Total Units : 10786 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/08/2008 Notice: C - CALL TO OFFICE 06/04/2024
Power Issued: 01/08/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M275789
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/14/2012 01/11/2013 DAH J G (180) (0) Y
INSPECTION COMMENTS: *RE: CAL.#48891*
 
(2) 02/20/2013 03/01/2013 GYM V E (270) (17) Y
INSPECTION COMMENTS: *SEE OBJECTIONS
 
(3) 03/22/2013 03/27/2013 CLC H X G (30) (0) Y
INSPECTION COMMENTS: *DO NOT SIGN OFF DRAWING - NOT APPROVED*
 
(4) 10/11/2017 10/12/2017 CLC V R (120) (6)
INSPECTION COMMENTS: INSPECTION FAIL 3 FT WORKING SPACE NOT PROVIDED IN FRONT OF ALL BUSWAYS SWITCHES, ACCESS TO APTS 5A,34C,31C,26A,25B, 23B, 22C, 22B NEED ACCESS TO MORE APTS
 
(5) 06/22/2021 06/23/2021 PHG J Y (48) (0)
INSPECTION COMMENTS: ADVISORY JOB TO BE MOVED TO NEW CONTRACTOR UNDER APP M00380721 FULL INSPECT NEEDED WITH NEW PLAN
 
(6) 10/27/2021 10/27/2021 MJD J Y (15) (0)
INSPECTION COMMENTS: FAIL, NEW APP OPEN TO SUPERSEDE M0038072, CONTRACTOR WILL REQUEST WITHDRAW AFTER FILING CORRECTIONS
 
(7) 06/03/2024 06/04/2024 FPY J X (5) (0) Y
INSPECTION COMMENTS: AS PER TUR CONTRACTOR TO SEND EMAIL TO MNELECTRICALIR@BUILDINGS.NYC.GOV TO REVIEW APPLICATIONS ATOI ANDREW
 
(8) 06/11/2024 06/11/2024 ASK C R (20) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. REF TO M00380721, MM08015957.

OBJECTION FOR APPLICATION #: M275789
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BSMT ROOF: LIMITED SERVICE FIRE PUMP SUPPLY CONDUCTORS NOT INSTALLED IN RIGID METAL CONDUITS.SECT.695.6(2)(CONT USED 2 1/2" EMT CONDUIT
RSLV 02/20/2013 03/22/2013 10/11/2017
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) ALL FLS: BEDROOMS RECEPTS & A/C RECEPTS 120 AMP
RSLV 02/20/2013 03/22/2013 10/11/2017
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) ALL FLS: PANELS IN ELECTRIC CLOSET
RSLV 02/20/2013 03/22/2013 10/11/2017
 
004 (999) OTHER
(ALL FLOORS)A) ALL FLS: EQUIPMENT BONDING JUMPER NOT PROVIDED TO BOND METAL BOX-ES AND WIRING DEVICE.. - ART.250.146,314.16(B)(4)ALL RECEPTS
RSLV 02/20/2013 03/22/2013 10/11/2017
 
005 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(ALL FLOORS)ALL FLS: ELECTRIC CLOSET ARMORED CABLES FEEDERS BRANCH WIRING
RSLV 02/20/2013 03/22/2013 10/11/2017
 
006 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS)ALL FLS: ELECTRIC CLOSET ARMORED CABLES FEEDERS BRANCH WIRING
RSLV 02/20/2013 03/22/2013 10/11/2017
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) ALL FLS: ELECTRIC CLOSET PANEL BLANKS
RSLV 02/20/2013 03/22/2013 10/11/2017
 
008 (999) OTHER
(ALL FLOORS)B) BSMT: ART.110.26 ONE DOOR MISSING PANIC HARDWARE FOR EGRESSES
RSLV 02/20/2013 03/22/2013 10/11/2017
 
009 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS) ALL FL: ELECTRIC CLOSET SPLICE BOXES
RSLV 02/20/2013 03/22/2013 10/11/2017
 
010 (999) OTHER
(ALL FLOORS)C) BSMT: 200 AMP SPECIC SERVICE SW FIRE PUMP NEUTRAL BAR IS NOT BOND-ED........... - ART.250.28
RSLV 02/20/2013 03/22/2013 10/11/2017
 
011 (999) OTHER
(ALL FLOORS)D) BSMT: 1- 60 AMP,2- 30 AMP SERVICE SWS NEUTRAL BAR IS NOT BONDED- ART.250.28
RSLV 02/20/2013 03/22/2013 10/11/2017
 
012 (999) OTHER
(ALL FLOORS)E) BSMT: 2- 30 AMP SERVUCE SWS NOT NEUTRAL PROVIDED WITH SERVICE EMT- ART.250.24(B)
RSLV 02/20/2013 03/22/2013 10/11/2017
 
013 (999) OTHER
(ALL FLOORS)F) BSMT: LINE AND LOAD IN SAME RACEWAY..... - ART.230.7
RSLV 02/20/2013 03/22/2013 10/11/2017
 
014 (999) OTHER
(ALL FLOORS)G) BSMT: MANUAL FIRE PUMP SERVICE SW 2500 AMP NOT ENCASE IN 2" OFCONCRETE........ - ART.695.6(B)
RSLV 02/20/2013 03/22/2013 10/11/2017
 
015 (999) OTHER
(ALL FLOORS)H) BSMT: MORE THAN 6 SERVICE SWS PROVIDED.... - ART.230.71
RSLV 02/20/2013 03/22/2013 10/11/2017
 
016 (999) OTHER
(ALL FLOORS)BSMT: 1- 200 AMP,1- 600 AMP,2- 30 AMP SERVICE ENTRANCE CONDUIT NOTBONDED...... - 250.92A
RSLV 02/20/2013 03/22/2013 10/11/2017
 
017 (999) OTHER
(ALL FLOORS)BSMT: PHASE AND NEUTRAL NOT GROUPED 2- 30 AMP SERVICE SWS.... -ART.300.2,300.3(B)
RSLV 02/20/2013 03/22/2013 10/11/2017
 
018 (999) OTHER
(ALL FLOORS)WORKING SPACE IN FRONT OF BUS DUCT SWITCHES NOT PROVIDED TABLE110.26 A 1
RSLV 10/11/2017 10/11/2017 06/11/2024
 
019 (999) OTHER
(ALL FLOORS) BUSWAYS NOT MARK WITH CURRENT RATING 368.120
RSLV 10/11/2017 10/11/2017 06/22/2021
 
020 (999) OTHER
(ALL FLOORS)BUSWAYS 4 INCH HIGH CURB NOT PROVIDED ALL FLOORS 368.10 C 2
RSLV 10/11/2017 10/11/2017 10/27/2021
 
021 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NEUTRAL NOT BONDED IN MAIN SERVICE EQUIPMENT 250.24 A 4
RSLV 10/11/2017 10/11/2017 10/27/2021
 
022 (999) OTHER
(BASEMENT) FIRE PUMP SERVICE SWITCH E.G.C UNDER SIZED 250.122
RSLV 10/11/2017 10/11/2017 06/22/2021
 
023 (999) OTHER
(BASEMENT) FIRE PUMP CONTROL WIRING RAN IN EMT 695.14 E NYC AMEND
RSLV 10/11/2017 10/11/2017 06/22/2021