| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1-100AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
3 |
2-800AMP, 1-1200AMP |
| E. Over 1200 AMPS |
3 |
1-2500AMP, 2-3000AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
11 |
11-500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
110 |
110-1 PHASE 24 CIRCUIT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
8 |
8-225AMPS 42CIRCUIT PANEL |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
12/14/2012 |
01/11/2013 |
DAH |
J |
|
G |
(180) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
*RE: CAL.#48891*
|
| |
| (2) |
02/20/2013 |
03/01/2013 |
GYM |
V |
|
E |
(270) |
|
(17) |
Y |
| INSPECTION COMMENTS:
|
*SEE OBJECTIONS
|
| |
| (3) |
03/22/2013 |
03/27/2013 |
CLC |
H |
X |
G |
(30) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
*DO NOT SIGN OFF DRAWING - NOT APPROVED*
|
| |
| (4) |
10/11/2017 |
10/12/2017 |
CLC |
V |
R |
|
(120) |
|
(6) |
|
| INSPECTION COMMENTS:
|
INSPECTION FAIL 3 FT WORKING SPACE NOT PROVIDED IN FRONT OF ALL BUSWAYS SWITCHES, ACCESS TO APTS 5A,34C,31C,26A,25B, 23B, 22C, 22B NEED ACCESS TO MORE APTS
|
| |
| (5) |
06/22/2021 |
06/23/2021 |
PHG |
J |
Y |
|
(48) |
|
(0) |
|
| INSPECTION COMMENTS:
|
ADVISORY JOB TO BE MOVED TO NEW CONTRACTOR UNDER APP M00380721 FULL INSPECT NEEDED WITH NEW PLAN
|
| |
| (6) |
10/27/2021 |
10/27/2021 |
MJD |
J |
Y |
|
(15) |
|
(0) |
|
| INSPECTION COMMENTS:
|
FAIL, NEW APP OPEN TO SUPERSEDE M0038072, CONTRACTOR WILL REQUEST WITHDRAW AFTER FILING CORRECTIONS
|
| |
| (7) |
06/03/2024 |
06/04/2024 |
FPY |
J |
X |
|
(5) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
AS PER TUR CONTRACTOR TO SEND EMAIL TO MNELECTRICALIR@BUILDINGS.NYC.GOV TO REVIEW APPLICATIONS ATOI ANDREW
|
| |
| (8) |
06/11/2024 |
06/11/2024 |
ASK |
C |
R |
|
(20) |
|
(0) |
|
| INSPECTION COMMENTS:
|
PASS. INSPECTION COMPLETE. REF TO M00380721, MM08015957.
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)BSMT ROOF: LIMITED SERVICE FIRE PUMP SUPPLY CONDUCTORS NOT INSTALLED IN RIGID METAL CONDUITS.SECT.695.6(2)(CONT USED 2 1/2" EMT CONDUIT |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) ALL FLS: BEDROOMS RECEPTS & A/C RECEPTS 120 AMP |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) ALL FLS: PANELS IN ELECTRIC CLOSET |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)A) ALL FLS: EQUIPMENT BONDING JUMPER NOT PROVIDED TO BOND METAL BOX-ES AND WIRING DEVICE.. - ART.250.146,314.16(B)(4)ALL RECEPTS |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 005 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (ALL FLOORS)ALL FLS: ELECTRIC CLOSET ARMORED CABLES FEEDERS BRANCH WIRING |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 006 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS)ALL FLS: ELECTRIC CLOSET ARMORED CABLES FEEDERS BRANCH WIRING |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 007 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) ALL FLS: ELECTRIC CLOSET PANEL BLANKS |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)B) BSMT: ART.110.26 ONE DOOR MISSING PANIC HARDWARE FOR EGRESSES |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 009 |
( 30) |
OUTLET BOXES ARE NOT SECURED (ALL FLOORS) ALL FL: ELECTRIC CLOSET SPLICE BOXES |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)C) BSMT: 200 AMP SPECIC SERVICE SW FIRE PUMP NEUTRAL BAR IS NOT BOND-ED........... - ART.250.28 |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)D) BSMT: 1- 60 AMP,2- 30 AMP SERVICE SWS NEUTRAL BAR IS NOT BONDED- ART.250.28 |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)E) BSMT: 2- 30 AMP SERVUCE SWS NOT NEUTRAL PROVIDED WITH SERVICE EMT- ART.250.24(B) |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS)F) BSMT: LINE AND LOAD IN SAME RACEWAY..... - ART.230.7 |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)G) BSMT: MANUAL FIRE PUMP SERVICE SW 2500 AMP NOT ENCASE IN 2" OFCONCRETE........ - ART.695.6(B) |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS)H) BSMT: MORE THAN 6 SERVICE SWS PROVIDED.... - ART.230.71 |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 016 |
(999) |
OTHER (ALL FLOORS)BSMT: 1- 200 AMP,1- 600 AMP,2- 30 AMP SERVICE ENTRANCE CONDUIT NOTBONDED...... - 250.92A |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 017 |
(999) |
OTHER (ALL FLOORS)BSMT: PHASE AND NEUTRAL NOT GROUPED 2- 30 AMP SERVICE SWS.... -ART.300.2,300.3(B) |
RSLV |
02/20/2013 |
03/22/2013 |
10/11/2017 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)WORKING SPACE IN FRONT OF BUS DUCT SWITCHES NOT PROVIDED TABLE110.26 A 1 |
RSLV |
10/11/2017 |
10/11/2017 |
06/11/2024 |
| |
| 019 |
(999) |
OTHER (ALL FLOORS) BUSWAYS NOT MARK WITH CURRENT RATING 368.120 |
RSLV |
10/11/2017 |
10/11/2017 |
06/22/2021 |
| |
| 020 |
(999) |
OTHER (ALL FLOORS)BUSWAYS 4 INCH HIGH CURB NOT PROVIDED ALL FLOORS 368.10 C 2 |
RSLV |
10/11/2017 |
10/11/2017 |
10/27/2021 |
| |
| 021 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) NEUTRAL NOT BONDED IN MAIN SERVICE EQUIPMENT 250.24 A 4 |
RSLV |
10/11/2017 |
10/11/2017 |
10/27/2021 |
| |
| 022 |
(999) |
OTHER (BASEMENT) FIRE PUMP SERVICE SWITCH E.G.C UNDER SIZED 250.122 |
RSLV |
10/11/2017 |
10/11/2017 |
06/22/2021 |
| |
| 023 |
(999) |
OTHER (BASEMENT) FIRE PUMP CONTROL WIRING RAN IN EMT 695.14 E NYC AMEND |
RSLV |
10/11/2017 |
10/11/2017 |
06/22/2021 |