BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M275027
Premises: 63 WEST 35 STREET MANHATTAN BIN: 1015885     Block: 837   Lot: 6
   
Application Completed and Certified

Filed: 63 W 35 ST Census Tract:   84 Health Area:  5200
6 AVENUE Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
Special Place Name:   MIDTOWN
Related Job Number:    104676511
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 04/23/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/11/2007 10:32 AM
Application Entered:   12/11/2007 Job Start Date:   01/01/2008
Last Change:   04/23/2009 Job End Date:   05/26/2009
Appointment Status:   
Last Inspection By:   REDDINGTON, J.       On     04/07/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011297 Licensee Name: PETROS KALEMKERIDIS
Firm: 002650 Firm Name: SIGMA ELECTRIC INC.
Firm Phone: 718-545-1619  Firm Address: 65-21 GRAND AVENUE MASPETH NY 11378 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   48291     Submittal #: 07A0536  
Owner / Occup:
Owner Business Name: FLINTLOCK
Authorized Representative:  JONATHAN ASCH
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  5000AMP, SERVICE SWITCH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  35  35 SETS OF 3/0, 4 WIRE
D. Over 250 MCM  20  20 SETS OF 500 MCM, 4WIRE
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  39  39 CKT, 4WIRE PANELS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  
B. Each Additional 10 Floors Or Less  3  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                   50     1200 
Total Units : 1250 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/11/2007 Notice: 1 - FIRST NOTICE 03/18/2009
Power Issued: 12/11/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MAIN ELECTRIC ROOM EQUIPTMENT.IP45264,IP45263

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M275027
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/10/2009 03/18/2009 JSB A E (330) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/07/2009 04/22/2009 SR2 C R E (75) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M275027
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ENTIRE: BUSS DUCT DISC SWITCHES ENTIRE BUILDING FUSES NOT CO-ORDIN-ATED.........24.12
RSLV 03/10/2009 03/10/2009 04/07/2009
 
002 (999) OTHER
A) BSMT & ROOF: TRANS DISC SWITCHES 277/840 NO MIGB'S USED250.97
RSLV 03/10/2009 03/10/2009 04/07/2009
 
003 (999) OTHER
B) ROOF: LIMITED SVC FIRE PUMP RACEWAY TO (LSVC FP) NO RIGID CONDUIT695.6(B)(2)
RSLV 03/10/2009 03/10/2009 04/07/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.