Electrical Application Details for App #: M274528
Premises: 78 LAIGHT STREET MANHATTAN BIN: 1087869     Block: 218   Lot: 14
   
Application Completed and Certified

Filed: 78 LAIGHT ST Census Tract:   39 Health Area:  7700
LAIGHT STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104566989
DOB Cross Street(s):   WASHINGTON STREET,    WEST STREET
Status:   C - JOB IS SIGNED OFF 05/24/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/26/2007 10:22 AM
Application Entered:   11/26/2007 Job Start Date:   11/27/2007
Last Change:   05/24/2008 Job End Date:   03/27/2008
Appointment Status:   
Last Inspection By:   REDDINGTON, J.       On     05/22/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010913 Licensee Name: JOHN MARI, JR.
Firm: 002201 Firm Name: MARI ELEC. CONTR'S INC.
Firm Phone: 718-815-1700  Firm Address: 463 WILD AVE STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $2,654.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOE SCARPANITO
Owner Business Name: DENALI CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  3 200 AMP
C. 201 Up to 600 AMPS  2  2 600 AMP 3 PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  8  8 SET OF 3 ORT
D. Over 250 MCM  4  4 SET OF 350 MCM 3 PHASE
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  8  200 AMP 1 PHASE
C. 3 Phase Up to 225 AMPS  1  200 AMP 3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  6 FLOORS
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 121  273    111  121     100     4000      
Total Units : 4726 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/26/2007 Notice: 1 - FIRST NOTICE 05/14/2008
Power Issued: 11/26/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M274528
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/06/2008 05/14/2008 CCH A E (150) (6) Y
INSPECTION COMMENTS: *APPOINTMENT NOT COMPLETE - WALK THROUGH ONLY* SEE VIOLATION DETAILS
 
(2) 05/22/2008 05/24/2008 SR2 C R E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M274528
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT: SER SW 200A NO NEUTRAL250.24B
RSLV 05/06/2008 05/06/2008 05/22/2008
 
002 (999) OTHER
BASEMENT: SER SWS NEUTRAL NOT BONDED250.28
RSLV 05/06/2008 05/06/2008 05/22/2008
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT: RACEWAY TO SER SWS NOT BONDED AND UNDER SIZE
RSLV 05/06/2008 05/06/2008 05/22/2008
 
004 (999) OTHER
BASEMENT: FIRE PUMP SER SWITCH LINE NOT SEPARATED300.5.G
RSLV 05/06/2008 05/06/2008 05/22/2008
 
005 (999) OTHER
BASEMENT: WATER GROUND RACEWAY NOT CONTINIOUS250.64.E
RSLV 05/06/2008 05/06/2008 05/22/2008
 
006 (999) OTHER
BASEMENT: OVER 42 CIR IN PANEL (PENTHOUSE AND BASEMENT)408.35....*NOT FINAL*
RSLV 05/06/2008 05/06/2008 05/22/2008