| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
600A SS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
3/0 |
| D. Over 250 MCM |
2 |
500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
42C |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT,SER EQUIPT, THERE IS MORE THEAN 7 SER SW |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT WATER MAIN,METER, WATER METER NOT JUMPER |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 003 |
(999) |
OTHER OUTDOOR A/C UNITS 620.22B, NO FRCI PROVIDED |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 004 |
( 26) |
ARMORED CABLES ARE INSTALLED EXPOSED CEILING BOX THRUOUT BX NOT PROPERLY SUPPORTED |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 005 |
( 50) |
TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING GRD FL CEILING, TEMP WIRING NOT REMOVED |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 1ST FL SUB PNLS, NO DIRECTORY PROVIDED |
RSLV |
06/03/2008 |
06/03/2008 |
01/26/2009 |
| |
| 007 |
(999) |
OTHER BSMT,100 DISCONN BY TRANSFORMER NEUTRAL BONDED 250.24A5 |
OPEN |
01/26/2009 |
01/26/2009 |
|
| |
| 008 |
(999) |
OTHER BSMT,800 DISCONN COND. IN PARALLEL NOT TERMINATED IN SAME MANNER 310.4 |
OPEN |
01/26/2009 |
01/26/2009 |
|