| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
|
| D. Over 250 MCM |
5 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
14 |
|
| D. 3 Phase Over 225 AMPS |
1 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
3 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (A)BSMT,FIRE PUMP SER SW NO NEUTRAL 250.24.B |
RSLV |
09/24/2009 |
09/24/2009 |
11/17/2009 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (A)BSMT,FIRE PUMP SER SW FEED FROM NEXT SER SW |
RSLV |
09/24/2009 |
11/17/2009 |
02/09/2010 |
| |
| 003 |
(999) |
OTHER (B)BSMT,PLP NEUTRAL BONDED 250.24.A5 |
RSLV |
09/24/2009 |
09/24/2009 |
11/17/2009 |
| |
| 004 |
(999) |
OTHER (C)ROOF,GENERATORS SW NEUTRAL BONDED 250.24.A5 |
RSLV |
09/24/2009 |
09/24/2009 |
11/17/2009 |
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE (B)ALL FL,FEEDER TO FLOWER GREEN WIRE USE ON PHASE |
RSLV |
09/24/2009 |
09/24/2009 |
11/17/2009 |
| |
| 006 |
(999) |
OTHER (D)BSMT ELEVATOR RM DIS SW NEUTRAL BONDED 250.24.A.5 |
RSLV |
09/24/2009 |
09/24/2009 |
11/17/2009 |
| |
| 007 |
(999) |
OTHER (E)CONDUCTOR NOT SUPPORTED IN RACEWAY FROM BASEMENT TO ROOF TAB 30019A,NOT A FINAL INSPECTION |
RSLV |
09/24/2009 |
11/17/2009 |
02/09/2010 |
| |
| 008 |
(999) |
OTHER A) 10 & 5TH FLRS: CONDUCTORS NOT PROPERLY SUPPORTED IN RACEWAY FROMBASEMENT TO ROOF........TAB 300.19A |
RSLV |
02/09/2010 |
02/09/2010 |
05/03/2010 |
| |
| 009 |
(999) |
OTHER B) BSMT: FIRE PUMP SER SWITCH NEUTRAL NOT BONDED.....250.28 |
RSLV |
02/09/2010 |
02/09/2010 |
05/03/2010 |