Electrical Application Details for App #: M269549
Premises: 48 MULBERRY STREET MANHATTAN BIN: 1086195     Block: 164   Lot: 9
   
Application Completed and Certified

Filed: 52 MULBERRY ST Census Tract:   29 Health Area:  7700
BASEMEMT-13 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   103
Related Job Number:    104540775
DOB Cross Street(s):   MOSCO STREET,    BAYARD STREET
Status:   C - JOB IS SIGNED OFF 05/06/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/13/2007 12:00 PM
Application Entered:   07/13/2007 Job Start Date:   07/16/2007
Last Change:   05/06/2010 Job End Date:   07/15/2008
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     05/03/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011902 Licensee Name: YU T IP
Firm: 003530 Firm Name: I.P. ELECTRIC INC
Firm Phone: 718-788-8875  Firm Address: 143 30TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,582.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KUN K MA
Owner Business Name: RICE BOWL REALTY CORP
Authorized Representative:  KUN MA
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  5  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  14  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  3  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 450  160    70  450     40           
Total Units : 1170 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 14 #10-Wire 1
Existing Meters 0 + New Meters 15 - Removed Meters 0 = Total Meters 15

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/13/2007 Notice: 1 - FIRST NOTICE 02/17/2010
Power Issued: 07/13/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M269549
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/24/2009 10/02/2009 CCH V G (135) (7) Y
INSPECTION COMMENTS: NO ACCESS TO ELEVATOR
 
(2) 11/17/2009 11/24/2009 CCH V Y G (135) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 02/09/2010 02/17/2010 CCH A R E (90) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(4) 05/03/2010 05/06/2010 CLC C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M269549
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(A)BSMT,FIRE PUMP SER SW NO NEUTRAL 250.24.B
RSLV 09/24/2009 09/24/2009 11/17/2009
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(A)BSMT,FIRE PUMP SER SW FEED FROM NEXT SER SW
RSLV 09/24/2009 11/17/2009 02/09/2010
 
003 (999) OTHER
(B)BSMT,PLP NEUTRAL BONDED 250.24.A5
RSLV 09/24/2009 09/24/2009 11/17/2009
 
004 (999) OTHER
(C)ROOF,GENERATORS SW NEUTRAL BONDED 250.24.A5
RSLV 09/24/2009 09/24/2009 11/17/2009
 
005 ( 19) DEFECTIVE WIRING IS IN USE
(B)ALL FL,FEEDER TO FLOWER GREEN WIRE USE ON PHASE
RSLV 09/24/2009 09/24/2009 11/17/2009
 
006 (999) OTHER
(D)BSMT ELEVATOR RM DIS SW NEUTRAL BONDED 250.24.A.5
RSLV 09/24/2009 09/24/2009 11/17/2009
 
007 (999) OTHER
(E)CONDUCTOR NOT SUPPORTED IN RACEWAY FROM BASEMENT TO ROOF TAB 30019A,NOT A FINAL INSPECTION
RSLV 09/24/2009 11/17/2009 02/09/2010
 
008 (999) OTHER
A) 10 & 5TH FLRS: CONDUCTORS NOT PROPERLY SUPPORTED IN RACEWAY FROMBASEMENT TO ROOF........TAB 300.19A
RSLV 02/09/2010 02/09/2010 05/03/2010
 
009 (999) OTHER
B) BSMT: FIRE PUMP SER SWITCH NEUTRAL NOT BONDED.....250.28
RSLV 02/09/2010 02/09/2010 05/03/2010