BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M268871
Premises: 550 HUDSON STREET MANHATTAN BIN: 1011229     Block: 621   Lot: 8
   
Application Completed and Certified

Filed: 550 HUDSON ST Census Tract:   73 Health Area:  6400
FIRST FLOOR AND CELLAR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   CHARLES STREET,    PERRY STREET
Status:   C - JOB IS SIGNED OFF 03/04/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/28/2007 9:54 AM
Application Entered:   06/28/2007 Job Start Date:   07/02/2007
Last Change:   03/04/2011 Job End Date:   11/02/2007
Appointment Status:   
Last Inspection By:   MCKENZIE, W.       On     11/22/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011509 Licensee Name: MORGAN J TOREN
Firm: 002978 Firm Name: A.C. MORGAN ELECTRIC
Firm Phone: 718-549-6800  Firm Address: 3601 RIVERDALE AVENUE BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTUARUANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EBS BUILDERS
Authorized Representative:  ANTHONY BONADUCE
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4 #3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/28/2007 Notice: 1 - FIRST NOTICE 03/09/2010
Power Issued: 06/28/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M268871
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/10/2009 03/18/2009 CCH A E (45) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 07/15/2009 07/29/2009 SR2 N (15) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 08/31/2009 09/09/2009 SR2 H X (30) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 11/18/2009 11/25/2009 CCH A R E (30) (3) Y
INSPECTION COMMENTS: NONE
 
(5) 03/02/2010 03/09/2010 NEI A R B (30) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(6) 11/22/2010 11/29/2010 WMK C R E (20) (0) Y
INSPECTION COMMENTS: SER & METER REPLACEMENT ONLY

OBJECTION FOR APPLICATION #: M268871
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
A) SER RM: NO WATER GROUND
RSLV 03/10/2009 08/31/2009 11/18/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
B) SER RM: NO SUPP.GROUND
RSLV 03/10/2009 08/31/2009 11/18/2009
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
A) SER RM: NEUTRAL NOT BONDED
RSLV 03/10/2009 08/31/2009 11/18/2009
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
B) SER RM: NO MIGB BUSHING
RSLV 03/10/2009 08/31/2009 11/18/2009
 
005 (999) OTHER
BASEMENT,WATER GROUND RACEWAY NOT CONTINOUS 250.64C
RSLV 11/18/2009 11/18/2009 03/02/2010
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(A)BASEMENT, SER SW NO MIG BUSHING
RSLV 11/18/2009 11/18/2009 03/02/2010
 
007 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(B)BASEMENT, 30A SER SW NO MIG BUSHING
RSLV 11/18/2009 11/18/2009 03/02/2010
 
008 (999) OTHER
BASEMENT: WATER GROUND RACEWAY NOT CONTINUOUS.......250.64C
RSLV 03/02/2010 03/02/2010 11/22/2010
 
009 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
A) BASEMENT: SER SW NO MIG BUSHING
RSLV 03/02/2010 03/02/2010 11/22/2010
 
010 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GROUND RACEWAY IS NOT CONTINUOUS AT WATER MAIN
RSLV 03/02/2010 03/02/2010 11/22/2010
 
011 (999) OTHER
SER ENT BONDING IS NOT OF PROPER SIZE......TAB 250.66BET EIB TO SER SW CONT USE #6 FOR 3/0
RSLV 03/02/2010 03/02/2010 11/22/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back