BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M267525
Premises: 234 THOMPSON STREET MANHATTAN BIN: 1008637     Block: 537   Lot: 13
   
Application Completed and Certified

Filed: 234 THOMPSON ST Census Tract:   65 Health Area:  5700
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   BLEECKER STREET,    WEST 3 STREET
Status:   C - JOB IS SIGNED OFF 02/03/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/23/2007 3:49 PM
Application Entered:   05/23/2007 Job Start Date:   05/29/2007
Last Change:   02/03/2011 Job End Date:   06/30/2007
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     04/21/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010273 Licensee Name: ROBERT K WITTMAN
Firm: 001467 Firm Name: URBAN-SERVWELL, INC.
Firm Phone: 212-534-3600  Firm Address: 856 EAST 136TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $865.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (5  Stores, 24 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRUCE RITTENBURG
Owner Business Name: TIME EQUITIES
Authorized Representative:  BRUCE RITTENBURG
Relationship To Owner:   DIRECTOR OF CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  200AMP 3SET OF 3/0
D. 601 Up to 1200 AMPS  1  600AMP2SETS OF 350,000
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  3/0
D. Over 250 MCM  2  350,000
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 27 #4-Wire 2 #10-Wire 0
Existing Meters 29 + New Meters 0 - Removed Meters 0 = Total Meters 29

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/23/2007 Notice: 1 - FIRST NOTICE 07/29/2009
Power Issued: 05/23/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE OLD END BOX WITH NEW APPROVED TYPE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M267525
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/07/2008 01/09/2008 FRI V E (15) (1) Y
INSPECTION COMMENTS: NONE
 
(2) 07/23/2009 07/29/2009 CCH A R E (60) (4) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 04/21/2010 04/27/2010 DAH C R (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M267525
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: 500KCM CONDUCTORS FUSED AT 500 AMPS
RSLV 01/07/2008 01/07/2008 07/23/2009
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(A)SER SW, NEUTRAL NOT BONDED (CANDY STORE)
RSLV 07/23/2009 07/23/2009 04/21/2010
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(B)SER SW RACE WAY NOT BONDED NEUTRAL BONDED
RSLV 07/23/2009 07/23/2009 04/21/2010
 
004 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
SER SW, LINE ON LOAD
RSLV 07/23/2009 07/23/2009 04/21/2010
 
005 (999) OTHER
SER SW 600A BONDING TO SMALL 250.66, NOT FINAL
RSLV 07/23/2009 07/23/2009 04/21/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.