BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M266807
Premises: 54 FRANKLIN STREET MANHATTAN BIN: 1001872     Block: 172   Lot: 30
   
Application Completed and Certified

Filed: 54-56 FRANKLIN ST Census Tract:   31 Health Area:  7700
STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   LAFAYETTE STREET,    BENSON PLACE
Status:   C - JOB IS SIGNED OFF 10/09/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/07/2007 10:27 PM
Application Entered:   05/07/2007 Job Start Date:   05/08/2007
Last Change:   10/09/2015 Job End Date:   10/30/2007
Appointment Status:   
Last Inspection By:   KELLER, JONATHAN       On     07/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012021 Licensee Name: VAN P VASSELL
Firm: 003699 Firm Name: V. VASS ELECTRIC CORP
Firm Phone: 718-325-7830  Firm Address: 3542 EASTCHESTER ROAD BRONX NY 10469 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $40.50
Other Work:   BRIDGE LIGHTING
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   STREET
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ADVANCED INSTALLATIONS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                     
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  05/27/2008
Power Issued: Response: V - OBJ WAS REMOVED 06/18/2008

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING FOR 82 LINEAR FEET OF SIDEWALK BRIDGE,6 LIGHT FIXTURES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M266807
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/05/2008 05/27/2008 NEI A (30) (5)
INSPECTION COMMENTS: *FIX'S ARE NOT 200 WATTS* SEE VIOLATION DETAILS
 
(2) 07/23/2015 08/03/2015 JKE C R (5) (0) Y
INSPECTION COMMENTS: NO SHED

OBJECTION FOR APPLICATION #: M266807
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
RMT USED OUTSIDE358.12.7..AMENDMENT
RSLV 05/05/2008 05/05/2008 07/23/2015
 
002 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
PORCELAIN FIXTURES IN USE
RSLV 05/05/2008 05/05/2008 07/23/2015
 
003 (999) OTHER
ROMEX IN USE334.12.10.D
RSLV 05/05/2008 05/05/2008 07/23/2015
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
NO G.F.C.I PROVIDED
RSLV 05/05/2008 05/05/2008 07/23/2015
 
005 (999) OTHER
FIX ARE NOT VANDEL PROOF590.4(F)
RSLV 05/05/2008 05/05/2008 07/23/2015