BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M265113
Premises: 261 WEST 28 STREET MANHATTAN BIN: 1087714     Block: 778   Lot: 1
   
Application Completed and Certified

Filed: 261 W 28 ST Census Tract:   95 Health Area:  5200
STREET LEVEL Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
Related Job Number:    104284212
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 09/09/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/29/2007 4:06 PM
Application Entered:   03/29/2007 Job Start Date:   03/29/2007
Last Change:   09/09/2008 Job End Date:   03/29/2008
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     09/03/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011658 Licensee Name: VITO CAPIZZO
Firm: 002661 Firm Name: S. J. ELECTRIC INC.
Firm Phone: 718-643-7274  Firm Address: 94-02 LINDEN BLVD OZONE PARK NY 11417 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
9 - OTHER
Total Fee:  $42.50
Other Work:   BRIDGE LIGHTING
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EVAN HAYMES
Owner Business Name: 261 WEST LLC
Authorized Representative:  EVAN HAYMES
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 10        10                
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/15/2008
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SIDEWALK SHED BRIDGE LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M265113
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/26/2008 05/03/2008 EBA A (30) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 05/07/2008 05/15/2008 RID V R (15) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 09/03/2008 09/09/2008 CLC C R (15) (0) Y
INSPECTION COMMENTS: SHED REMOVED BEFORE INSPECTION

OBJECTION FOR APPLICATION #: M265113
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SHED: EMT USED OUTSIDE358.12.7
RSLV 04/26/2008 04/26/2008 05/07/2008
 
002 (999) OTHER
SHED: ROMEX FEEDS SHED LIGHTS334.12.B2
RSLV 04/26/2008 04/26/2008 05/07/2008
 
003 (999) OTHER
SHED: 1900 BOX USED OUTSIDE314.15
RSLV 04/26/2008 04/26/2008 05/07/2008
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
SHED: NO G.F.I.PROTECTION
RSLV 04/26/2008 04/26/2008 05/07/2008
 
005 (999) OTHER
A) OUTDOOR BRIDGE LIGHTING.....410.12COMM: FIXTURES USED OUTDOOR NOT APPROVED
RSLV 05/07/2008 05/07/2008 09/03/2008
 
006 (999) OTHER
B) OUTDOOR BRIDGE LIGHTING....334.12COMM: ROMEX USED OUTDOOR
RSLV 05/07/2008 05/07/2008 09/03/2008
 
007 (999) OTHER
C) OUTDOOR BRIDGE LIGHTING....358.26COMM: USED EMT OUTDOOR
RSLV 05/07/2008 05/07/2008 09/03/2008
 
008 (999) OTHER
D) OUTDOOR BRIDGE LIGHTING....590.6COMM: NO G.F.C.I
RSLV 05/07/2008 05/07/2008 09/03/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.