Electrical Application Details for App #: M263694
Premises: 82 UNIVERSITY PLACE MANHATTAN BIN: 1009286     Block: 569   Lot: 27
   
Application Completed and Certified

Filed: 82 UNIVERSITY PL Census Tract:   61 Health Area:  5700
CELLAR TO 9TH FLOOR, ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Related Job Number:    104054372
DOB Cross Street(s):   EAST 11 STREET,    EAST 12 STREET
Status:   C - JOB IS SIGNED OFF 11/13/2009 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/26/2007 4:39 PM
Application Entered:   02/26/2007 Job Start Date:   02/28/2007
Last Change:   11/13/2009 Job End Date:   11/30/2007
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     09/02/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010786 Licensee Name: JOE ZAGO
Firm: 003185 Firm Name: COMPSEC ELECTRIC CORP.
Firm Phone: 718-392-2540  Firm Address: 27-01 41 AVE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,161.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 10 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL DILIBERTO
Owner Business Name: 82 UNIVERSITY PL. CORP.
Authorized Representative:  GINO CALLEO
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3PH 400A
D. 601 Up to 1200 AMPS  2   3PH 800A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  4 # 500MCM EA. SET
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  100A 8/16CT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 150  250  25  50  200     100           
Total Units : 775 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 0 #10-Wire 2
Existing Meters 2 + New Meters 12 - Removed Meters 2 = Total Meters 12

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/26/2007 Notice: 1 - FIRST NOTICE 07/29/2009
Power Issued: 02/26/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  I WILL BE WIRING ALL BUILDING. ( 10 APARTMENTS AND 1ST FLOOR COMMERCIAL SPACE).

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M263694
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2009 07/29/2009 CCH A G (105) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 09/02/2009 09/08/2009 CCH C R E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M263694
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SER RM FUSE CUT OUT BOX PULL BOX NOT BONDED
RSLV 07/23/2009 07/23/2009 09/02/2009
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
SER RM GROUND RACEWAY
RSLV 07/23/2009 07/23/2009 09/02/2009
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SER R BX CABLE SLEEVE 3/4" NEED CONNECTOR
RSLV 07/23/2009 07/23/2009 09/02/2009
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
9TH FL, KITCHEN OUTLET NOT GFCI
RSLV 07/23/2009 07/23/2009 09/02/2009
 
005 ( 19) DEFECTIVE WIRING IS IN USE
BED RM, ARC FAULT DEFECTIVE
RSLV 07/23/2009 07/23/2009 09/02/2009