| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (GROUND FLOOR) BATHROOM GFCI NOT WORKING PROPERLY. |
RSLV |
05/01/2018 |
05/01/2018 |
05/07/2018 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (GROUND FLOOR) OUT DOOR AC UNIT NOT PROPERLY GROUNDED. |
RSLV |
05/01/2018 |
05/01/2018 |
05/23/2018 |
| |
| 003 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) (GROUND FLOOR) OUT DOOR CONDUIT NOT PROPERLY SUPPORTED. |
RSLV |
05/01/2018 |
05/01/2018 |
05/07/2018 |
| |
| 004 |
(999) |
OTHER (GROUND FLOOR) AC UNIT OVER FUSED. 110.3 310.16 |
RSLV |
05/01/2018 |
05/01/2018 |
05/23/2018 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR) IN USE COVER ON OUTDOOR GFCI. |
RSLV |
05/01/2018 |
05/01/2018 |
05/23/2018 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR) 200A DISCONNECT SWITCH TERMINALS CORRODED. |
RSLV |
05/01/2018 |
05/01/2018 |
05/23/2018 |
| |
| 007 |
(999) |
OTHER (GROUND FLOOR) SERVICE SWITCH BLOCKED BY HEAVY EQUIPMENT. 110.26 |
RSLV |
05/01/2018 |
05/01/2018 |
05/23/2018 |
| |
| 008 |
(126) |
BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN (GROUND FLOOR) ARTICLE 250, WATER MAIN GROUND ARE NOT CONTINUOUS |
RSLV |
05/17/2018 |
05/17/2018 |
05/23/2018 |
| |
| 009 |
(999) |
OTHER (GROUND FLOOR)EQUIPMENT GROUNDING CONDUCTOR ARE NOT PROPERLY INSTALLED. |
RSLV |
05/17/2018 |
05/17/2018 |
05/23/2018 |
| |
| 010 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (GROUND FLOOR) COMMENT |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 011 |
(999) |
OTHER (GROUND FLOOR)HANDLE TIES NOT PROVIDED ON MULTIWIRE CIRCUITS ART. 210.4 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 012 |
(999) |
OTHER (GROUND FLOOR) MULTIWIRE CIRCUITS NOT GROUPED ART. 210.4 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 013 |
(999) |
OTHER (GROUND FLOOR) ARC FLUSH LABELS NOT PROVIDED T-OUT ART. 110.16 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 014 |
(999) |
OTHER (GROUND FLOOR) ELECTRICAL EQUIPMENT NOT PROPERLY MOUNTED ART. 110.13 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 015 |
(999) |
OTHER (GROUND FLOOR)OUTLET SET BACK IN COMBUSTIBLE MATERIAL T-OUT WOOD PANELS ART.314.20 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 016 |
(999) |
OTHER (GROUND FLOOR)WORKING SPACE NOT PROVIDED FOR OUTDOOR A/C DISCONNECT SWITCH ART.110.26 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |
| |
| 017 |
(999) |
OTHER (GROUND FLOOR) A/C DISCONNECT SWITCH USED AS RACEWAY ART. 312.8 |
RSLV |
05/07/2018 |
05/07/2018 |
05/23/2018 |