Electrical Application Details for App #: M250058
Premises: 134 WEST 46 STREET MANHATTAN BIN: 1022646     Block: 998   Lot: 50
   
Application Completed and Certified

Filed: 134 W 46 ST Census Tract:   119 Health Area:  5200
THROUGHOUT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10036 Community Board:   105
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 12/11/2013
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/24/2005 Job Start Date:   10/06/2005
Last Change:   12/11/2013 Job End Date:   12/15/2005
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     11/15/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $785.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   BAR- RESTURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAT BURKE
Owner Business Name: O'BRIANS IRISH PUB
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 100  70    30  110                
Total Units : 310 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/24/2005 Notice: 1 - FIRST NOTICE 03/23/2010
Power Issued: 10/24/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M250058
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/23/2009 02/27/2009 CLC A E (30) (9) Y
INSPECTION COMMENTS: *NEED ACCESS TO COMPRESSORS ON ROOF - NEXT INSPECTION* SEE VIOLATION DETAILS
 
(2) 03/19/2010 03/23/2010 DAH A Y B (25) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 11/15/2013 11/21/2013 DNM C R E (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M250058
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ENTIRE: PANELS NEUTRAL BONDED AFTER SER250.24.A5
RSLV 02/23/2009 02/23/2009 03/19/2010
 
002 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
2ND FLOOR: BEHIND BAR G.F.C.I
RSLV 02/23/2009 02/23/2009 03/19/2010
 
003 (999) OTHER
BSMT: 200 AMP SER SW BONDING UNDERSIZE250.66
RSLV 02/23/2009 03/19/2010 11/15/2013
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT: 200 AMP SER SW NEUTRAL NOT BONDED
RSLV 02/23/2009 02/23/2009 03/19/2010
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT: SPLICE BOX NEAR WATER METER
RSLV 02/23/2009 03/19/2010 11/15/2013
 
006 (999) OTHER
BSMT: SER GROUND RACEWAY NOT CONTINUOUS250
RSLV 02/23/2009 02/23/2009 03/19/2010
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: SER GROUND LOOSE AT WATER MAIN
RSLV 02/23/2009 02/23/2009 03/19/2010
 
008 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT: SER GROUND RACEWAY
RSLV 02/23/2009 02/23/2009 03/19/2010
 
009 (999) OTHER
BSMT
RSLV 02/23/2009 03/19/2010 11/15/2013
 
010 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT,SVC ENT 1 SET #600MCM FUSED AT 601A IN 800A TRANS CABINET 1 SET
RSLV 03/19/2010 03/19/2010 11/15/2013
 
011 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
FDR 1 SET 500 MCM FUSED AT 601A, NOT A FINAL INSPECTION
RSLV 03/19/2010 03/19/2010 11/15/2013