| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER ENTIRE: PANELS NEUTRAL BONDED AFTER SER250.24.A5 |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 002 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE 2ND FLOOR: BEHIND BAR G.F.C.I |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 003 |
(999) |
OTHER BSMT: 200 AMP SER SW BONDING UNDERSIZE250.66 |
RSLV |
02/23/2009 |
03/19/2010 |
11/15/2013 |
| |
| 004 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BSMT: 200 AMP SER SW NEUTRAL NOT BONDED |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 005 |
( 29) |
OUTLET BOXES ARE NOT COVERED BSMT: SPLICE BOX NEAR WATER METER |
RSLV |
02/23/2009 |
03/19/2010 |
11/15/2013 |
| |
| 006 |
(999) |
OTHER BSMT: SER GROUND RACEWAY NOT CONTINUOUS250 |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 007 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT: SER GROUND LOOSE AT WATER MAIN |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 008 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT: SER GROUND RACEWAY |
RSLV |
02/23/2009 |
02/23/2009 |
03/19/2010 |
| |
| 009 |
(999) |
OTHER BSMT |
RSLV |
02/23/2009 |
03/19/2010 |
11/15/2013 |
| |
| 010 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BSMT,SVC ENT 1 SET #600MCM FUSED AT 601A IN 800A TRANS CABINET 1 SET |
RSLV |
03/19/2010 |
03/19/2010 |
11/15/2013 |
| |
| 011 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE FDR 1 SET 500 MCM FUSED AT 601A, NOT A FINAL INSPECTION |
RSLV |
03/19/2010 |
03/19/2010 |
11/15/2013 |