BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M247538
Premises: 34 HUDSON STREET MANHATTAN BIN: 1001562     Block: 144   Lot: 16
   
Application Completed and Certified

Filed: 36-38 HUDSON ST Census Tract:   33 Health Area:  7700
8FLR,APT12A Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   DUANE STREET,    DUANE STREET
Status:   C - JOB IS SIGNED OFF 02/27/2009
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/27/2005 Job Start Date:   07/25/2005
Last Change:   02/27/2009 Job End Date:   12/20/2006
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     02/02/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011781 Licensee Name: THEODORE THEODOROPOULOS
Firm: 002302 Firm Name: T & T ELECTRICAL CORP.
Firm Phone: 718-721-3300  Firm Address: 24-30 47TH STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $3,393.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: JOSEPH LAMBARDI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  2  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  12  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  16  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  12  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 143  494  103  152  251     220           
Total Units : 1363 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 12 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/27/2005 Notice: 1 - FIRST NOTICE 03/11/2008
Power Issued: 07/27/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M247538
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2008 03/11/2008 CCH A E (120) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/02/2009 02/09/2009 CCH C R E (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M247538
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: FIRE PUMP CONTROLLER USED AS JUNCTION BOX695.6F
RSLV 03/04/2008 03/04/2008 02/02/2009
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT: 1200 AMP SER SW AND ELEVATOR DIS SWCOMM: FUSES NOT SAME SIZE
RSLV 03/04/2008 03/04/2008 02/02/2009