BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M245502
Premises: 37 7 AVENUE MANHATTAN BIN: 1010598     Block: 608   Lot: 9
   
Application Completed and Certified

Filed: 162 W 13 ST Census Tract:   71 Health Area:  6100
BASEMENT, 1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 12/12/2005
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/20/2005 Job Start Date:   06/15/2005
Last Change:   12/12/2005 Job End Date:   12/15/2005
Appointment Status:   
Last Inspection By:   DORSAINVILLE, R       On     11/22/2005      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010804 Licensee Name: SANG CHEUNG
Firm: 002065 Firm Name: AL-LECTRIC ELECT'L CONTRG
Firm Phone: 212-219-3336  Firm Address: 137 CHRYSTIE STREET NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $229.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   SUBWAY SANDWICH
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MICHAEL KUO
Owner Business Name: MICHELLE KUO CORPORATION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 20  26  12  20              
Total Units : 89 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/20/2005 Notice:  
Power Issued: 05/20/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADE THE EXISTING SERVICE AND BRANCH WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M245502
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/22/2005 11/30/2005 RID C E (30) (0)
INSPECTION COMMENTS: NONE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back