BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M239587
Premises: 113 AVENUE OF THE AMERICAS MANHATTAN BIN: 1088003     Block: 477   Lot: 64
   

Filed: 113 6 AV Census Tract:   51 Health Area:  6800
TO 117 6TH AVE-BSMT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   SULLIVAN STREET,    BROOME STREET
Status:   C - SIGNOFF IS AWAITING FEE PAYMENT 05/07/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/16/2004 Job Start Date:   10/27/2004
Last Change:   05/07/2015 Job End Date:   11/30/2004
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     04/28/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010628 Licensee Name: ROBERT SPALLINO
Firm: 001827 Firm Name: MAXIMUM ELEC'L CONTRG COR
Firm Phone: 718-882-4606  Firm Address: 708 MACE AVENUE BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: 117 6TH AVE CORP
Authorized Representative:   117 6TH AVE CORP
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/16/2004 Notice: 1 - FIRST NOTICE 03/04/2015
Power Issued: 11/16/2004 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M239587
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/17/2008 10/22/2008 FRI A E (30) (5) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 08/24/2009 08/26/2009 WMK A R B (120) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 02/26/2015 03/04/2015 BUR A Y E (60) (4) Y
INSPECTION COMMENTS: NONE
 
(4) 04/28/2015 05/07/2015 WYF C R E (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M239587
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERV.SW: NOT BONDED TO NEUTRAL
RSLV 10/17/2008 10/17/2008 08/24/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
SWRV.SW: WATER GROUND,SUPP'GROUND ABDENT
RSLV 10/17/2008 10/17/2008 08/24/2009
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SERV.SW: NOT BONDED TO ENCLOSURE - CONCENTRIC KO IN USE
RSLV 10/17/2008 10/17/2008 08/24/2009
 
004 ( 40) LOCKNUTS ARE MISSING OR LOOSE
SERV.SW: L/N LOOSE
RSLV 10/17/2008 10/17/2008 08/24/2009
 
005 ( 42) BUSHINGS ARE MISSING OR LOOSE
SERV.SW: BUSHING NOT PROVIDED
RSLV 10/17/2008 10/17/2008 08/24/2009
 
006 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
REST PNL: #6 WIRE FUSED 100A
RSLV 08/24/2009 08/24/2009 02/26/2015
 
007 (999) OTHER
REST PNL: MORE THAN 3 WIRE INSIDE GREENFIELD NOT DERATEDART.310.15(B)(2)(A)
RSLV 08/24/2009 08/24/2009 02/26/2015
 
008 (999) OTHER
REST PNL: EQUIPMENT GROUNDING NOT PROVIDED IN GREENFIELDART.250.118(6)(D)
RSLV 08/24/2009 08/24/2009 02/26/2015
 
009 (999) OTHER
REST PNL: SERVICE INSTALLED IN BATHROOMART.230.70A2
RSLV 08/24/2009 02/26/2015 04/28/2015
 
010 (999) OTHER
GROUND FLOOR END BOX NOT SUPPPORTED IN OUTBOOR AREA. 314.23
RSLV 02/26/2015 02/26/2015 04/28/2015
 
011 (999) OTHER
BATHROOM EMT CONDUIT NOT PROPERLY SUPPORTED AT PANEL 358.30
RSLV 02/26/2015 02/26/2015 04/28/2015
 
012 (999) OTHER
BATHROOM SERVICE ENTRANCE NOT BONDED WITH END BOX 250.92A
RSLV 02/26/2015 02/26/2015 04/28/2015
 
013 (999) OTHER
BATHROOM SUPPLEMENTRY GROUND NOT CONTINOUS. 300.16
RSLV 02/26/2015 02/26/2015 04/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.