| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER SERV.SW: NOT BONDED TO NEUTRAL |
RSLV |
10/17/2008 |
10/17/2008 |
08/24/2009 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY SWRV.SW: WATER GROUND,SUPP'GROUND ABDENT |
RSLV |
10/17/2008 |
10/17/2008 |
08/24/2009 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED SERV.SW: NOT BONDED TO ENCLOSURE - CONCENTRIC KO IN USE |
RSLV |
10/17/2008 |
10/17/2008 |
08/24/2009 |
| |
| 004 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE SERV.SW: L/N LOOSE |
RSLV |
10/17/2008 |
10/17/2008 |
08/24/2009 |
| |
| 005 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE SERV.SW: BUSHING NOT PROVIDED |
RSLV |
10/17/2008 |
10/17/2008 |
08/24/2009 |
| |
| 006 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE REST PNL: #6 WIRE FUSED 100A |
RSLV |
08/24/2009 |
08/24/2009 |
02/26/2015 |
| |
| 007 |
(999) |
OTHER REST PNL: MORE THAN 3 WIRE INSIDE GREENFIELD NOT DERATEDART.310.15(B)(2)(A) |
RSLV |
08/24/2009 |
08/24/2009 |
02/26/2015 |
| |
| 008 |
(999) |
OTHER REST PNL: EQUIPMENT GROUNDING NOT PROVIDED IN GREENFIELDART.250.118(6)(D) |
RSLV |
08/24/2009 |
08/24/2009 |
02/26/2015 |
| |
| 009 |
(999) |
OTHER REST PNL: SERVICE INSTALLED IN BATHROOMART.230.70A2 |
RSLV |
08/24/2009 |
02/26/2015 |
04/28/2015 |
| |
| 010 |
(999) |
OTHER GROUND FLOOR END BOX NOT SUPPPORTED IN OUTBOOR AREA. 314.23 |
RSLV |
02/26/2015 |
02/26/2015 |
04/28/2015 |
| |
| 011 |
(999) |
OTHER BATHROOM EMT CONDUIT NOT PROPERLY SUPPORTED AT PANEL 358.30 |
RSLV |
02/26/2015 |
02/26/2015 |
04/28/2015 |
| |
| 012 |
(999) |
OTHER BATHROOM SERVICE ENTRANCE NOT BONDED WITH END BOX 250.92A |
RSLV |
02/26/2015 |
02/26/2015 |
04/28/2015 |
| |
| 013 |
(999) |
OTHER BATHROOM SUPPLEMENTRY GROUND NOT CONTINOUS. 300.16 |
RSLV |
02/26/2015 |
02/26/2015 |
04/28/2015 |