BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M229217
Premises: 131 EAST 70 STREET MANHATTAN BIN: 1042723     Block: 1405   Lot: 14
   
Application Completed and Certified

Filed: 131 E 70 ST Census Tract:   128 Health Area:  4100
BSMT Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   PARK AVENUE,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 11/09/2012
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/04/2003 Job Start Date:   11/25/2003
Last Change:   11/09/2012 Job End Date:   12/25/2003
Appointment Status:   
Last Inspection By:   DONOVAN, JAMES       On     10/17/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010983 Licensee Name: JOSEPH J SGROI
Firm: 000794 Firm Name: JOSEPH SGROI & SONS, INC.
Firm Phone: 718-728-3510  Firm Address: 34-06 44TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $113.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: JUDSON REALTY INC
Authorized Representative:   JUDSON REALTY INC
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100 AMP PANEL M/L
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/04/2003 Notice: 1 - FIRST NOTICE 08/25/2012
Power Issued: 12/04/2003 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M229217
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2012 08/25/2012 IOS A G (45) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 09/05/2012 09/13/2012 IOS J Y G (1) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 10/17/2012 11/08/2012 JVA C R E (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M229217
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT: SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER... -250.92(A)
RSLV 08/15/2012 09/05/2012 10/17/2012
 
002 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
BASEMENT: NO GROUND ROD PROVIDED......... - 250.50
RSLV 08/15/2012 08/15/2012 09/05/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order