| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
|
| D. 601 Up to 1200 AMPS |
2 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
4 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
5 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BSMT: SERVICE EQUIPMENTCOM: SER ENTRANCE CONDUCTORS,SER,NEUTRAL BAR |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT: SERVICE GROUND CONDUCTORCOM: NO EARTH GROUND PROVIDED |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 003 |
(999) |
OTHER BSMT: 800 AMP SERVICE SWITCH.....240.12ACOM: SECOND FUSE NOT CO-ORDINATED (USED BREAKERS) |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 004 |
(999) |
OTHER BSMT: FIRE PUMP SERVICE.....695COM: LIMITED FIRE PUMP SER,NOT FUSE 150% |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 005 |
(999) |
OTHER ROOF: TOP MECHANICAL ROOM/PUMP ROOM.....620.22BCOM: NO G.F.C.I.PROVIDED |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 006 |
(999) |
OTHER THROUGH-OUT THE BUILDING BEDROOMS....210.12BCOM: NO ARC FAULT CIRCUIT PROVIDED BEDROOM |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 007 |
(999) |
OTHER THROUGH-OUT THE BUILDING KITCHEN OUTLETS....210.12ACOM: KITCHEN OUTLETS NOT 4FS BETWEEN COUNTER-TOP |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF TOP A/C UNITSCOM: NOT GROUNDED |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |
| |
| 009 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX ROOF TOP MECHANICAL ROOM*THIS IS NOT A FINAL INSPECTION* |
RSLV |
09/15/2008 |
07/10/2009 |
06/23/2010 |