Electrical Application Details for App #: M176227
Premises: 155 CHAMBERS STREET MANHATTAN BIN: 1001504     Block: 140   Lot: 9
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 155 CHAMBERS ST Census Tract:   21 Health Area:  7700
2ND FL Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/17/1999 Job Start Date:   03/03/1999
Last Change:   08/22/2025 Job End Date:   04/10/1999
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     02/06/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011288 Licensee Name: DENNIS KARAGOUNIS
Firm: 002217 Firm Name: YORK ELEC'L CONTR'S INC.
Firm Phone: 718-353-7227  Firm Address: 162-10 CROCHERON AVENUE FLUSHING NY 11358 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $19.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MAROB MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 10  20  14                  
Total Units : 46 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/06/2018
Power Issued: Response:  

Follow-Up:
Wires Comments: NEW WIRING THROUGHOUT THE APT
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M176227
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/06/2018 02/06/2018 PHG V (30) (4)
INSPECTION COMMENTS: DID NOT SEE AC UNITS. PANEL AND FEEDER NOT ON APP

OBJECTION FOR APPLICATION #: M176227
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 002) 12 WIRE ON 30 AMP BREAKER 240.4
OPEN 02/06/2018 02/06/2018
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 002) BOXS NOT SUPPORTED
OPEN 02/06/2018 02/06/2018
 
003 (999) OTHER
(FLOOR: 002) 3 WIRE CABLE ON SAME PHASE
OPEN 02/06/2018 02/06/2018
 
004 (999) OTHER
(FLOOR: 002) TRACK LIGHTS RUNNING THRU WALL 110.3
OPEN 02/06/2018 02/06/2018