BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M145123
Premises: 1045 MADISON AVENUE MANHATTAN BIN: 1046469     Block: 1491   Lot: 151
   

Filed: 1045 MADISON AV Census Tract:   142 Health Area:  3600
4883 2 Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   EAST 79 STREET,    EAST 80 STREET
Status:   K - CLOSED/CANCELLED 07/19/2005
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/29/1996 Job Start Date:   06/25/1996
Last Change:   07/19/2005 Job End Date:   07/19/1996
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     07/15/2005      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  

License #: 010779 Licensee Name: DAVID BELLASK
Firm: 000347 Firm Name: CONSOLIDATED ELE CONSTR
Firm Phone: 212-661-9555  Firm Address: 201 EAST 42ND STREET-11TH FL. NEW YORK NY 10017 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $14.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: TYBER INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   19                
Total Units : 27 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WORK LOCATED WITHIN TENENT STORE AREA

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M145123
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/23/1996 09/18/1996 MIR Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 09/20/1996 10/05/1996 MIR Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 07/15/2005 07/19/2005 ADM K (1) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back