BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M143654
Premises: 1464 1 AVENUE MANHATTAN BIN: 1045947     Block: 1471   Lot: 2
   
Application Completed and Certified

Filed: 1464 1 AV Census Tract:   132 Health Area:  4300
NONE Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):   EAST 76 STREET,    EAST 77 STREET
Status:   C - JOB IS SIGNED OFF 12/15/2009
Request Type:   C - COMPLAINT eFiled:   NO
Application Entered:   06/11/1996 Job Start Date:   08/30/1996
Last Change:   12/15/2009 Job End Date:   09/10/1996
Appointment Status:   
Last Inspection By:   HINDS EUGENE       On     12/04/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011026 Licensee Name: CHANG KEUN-SHIN
Firm: 002493 Firm Name: ASKO ELEC CONST & MAIN IN
Firm Phone: 718-786-8833  Firm Address: 21-24 39TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $25.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   PIZZA
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: NY PIZZA CAFE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 16    16              
Total Units : 40 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   9-5 Contact Phone:   212 535 1177

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  08/26/1996
Power Issued: Response: F - FILED TO REMOVE OBJECTION 08/30/1996

Follow-Up: X - FILED APPL,NOW CLOSED 08/30/1996
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M143654
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/20/1996 06/25/1996 GO1 W (15) (5)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 12/04/2009 12/15/2009 EHD C R (30) (0) Y
INSPECTION COMMENTS: INSTALL AND REMOVED




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order