BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M095874
Premises: 14 EAST 125 STREET MANHATTAN BIN: 1054016     Block: 1749   Lot: 64
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 14 E 125 ST Census Tract:   198 Health Area:  1600
A23/92 NONE Admin Area:   M - MANHATTAN Inspection Area:   H
NEW YORK, NY 10035 Community Board:   111
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/22/1992 Job Start Date:   06/17/1992
Last Change:   08/22/2025 Job End Date:   07/17/1992
Appointment Status:   
Last Inspection By:   IVEY, A.       On     05/09/1997      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 010464 Licensee Name: RALPH A PRINCIPE
Firm: 002932 Firm Name: STANCO ELEC'L CONTR'S INC
Firm Phone: 718-438-4505  Firm Address: 124 MC CLEAN AVENUE STATEN ISLAND NY 10305 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $22.00
Other Work:   OIL BURNER WIRING ONLY
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: HPD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M095874
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/24/1993 07/20/1995 X01 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 07/14/1995 07/20/1995 X01 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 05/09/1997 05/14/1997 IA1 N (15) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order