BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M029767
Premises: 135 SULLIVAN STREET MANHATTAN BIN: 1008039     Block: 517   Lot: 1
   
Application Completed and Certified

Filed: 135 SULLIVAN ST Census Tract:   49 Health Area:  6800
12187-1 NONE Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    WEST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 04/14/1988
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/04/1987 Job Start Date:   12/01/1987
Last Change:   03/11/1988 Job End Date:   12/15/1987
Appointment Status:   
Last Inspection By:   COLON, WILFREDO JR       On     02/29/1988      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 009606 Licensee Name: LEO GOODMAN
Firm: 001740 Firm Name: TRIAC ELECTRICAL CORP.
Firm Phone: 718-492-8050  Firm Address: 966 CONEY ISLAND AVENUE BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $36.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   ANTIQUES
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: VICTOR ANTIQUES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/04/1987 Notice:  
Power Issued: 12/07/1987 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M029767
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/25/1987 01/11/1988 WC1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 02/29/1988 03/11/1988 WC1 C E (40) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back