BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B437603
Premises: 44 BRIDGE STREET BROOKLYN BIN: 3395987     Block: 31   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 50 BRIDGE ST Census Tract:   21 Health Area:  1000
413 Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   PLYMOUTH STREET,    WATER STREET
Status:   C - JOB IS SIGNED OFF 04/21/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/24/2017 4:09 PM
Application Entered:   11/24/2017 Job Start Date:   01/29/2018
Last Change:   04/21/2018 Job End Date:   05/27/2018
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     04/18/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $60.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ZACHI OZERII
Owner Business Name: SANTA I. CONTRACTING CORP
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  413  14             
Buildings Total 14                
Total Units : 32 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 02/16/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACING CB PNL & LIGHTING DEVICES THROUGHOUT TO EXISTING WIRING. NEW BR. CIR TO HOT WATER HEATER AND NEW BRANCHCIRCUITS FOR KITCHEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B437603
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2018 01/29/2018 JKJ N (31) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 02/06/2018 02/06/2018 OSZ V (35) (3)
INSPECTION COMMENTS: CORRECT OBJECTION.
 
(3) 02/15/2018 02/16/2018 JKJ J X (22) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS
 
(4) 04/18/2018 04/18/2018 HMC C R (1) (0)
INSPECTION COMMENTS: PASSED BY INSPECTOR OSCAR ZELAYA, NOT SIGNED OFF IN BIZ.

OBJECTION FOR APPLICATION #: B437603
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 004)BREAKER IN PANEL FOR MONITORING SYSTEM OVER FUSED. ART. 240.3
RSLV 02/06/2018 02/06/2018 04/18/2018
 
002 (188) MEANS OF POWER DISCONNECT NOT PROVIDED AS PER CODE
(FLOOR: 004)NO MEANS OF DISCONNECT HAS BEEN PROVIDED FOR HOT WATER HEATER.645.10
RSLV 02/06/2018 02/06/2018 04/18/2018
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 004) KO IN PANEL. ART. 110.12(A)
RSLV 02/06/2018 02/06/2018 04/18/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.