Electrical Application Details for App #: B437262
Premises: 420 KENT AVENUE BROOKLYN BIN: 3425676     Block: 2134   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 420 KENT AV Census Tract:   547
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11249 Community Board:   301
Related Job Number:    320597476
DOB Cross Street(s):   SOUTH 8 STREET,    SOUTH 9 STREET
Status:   C - JOB IS SIGNED OFF 09/15/2020
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/15/2017 Job Start Date:   11/06/2017
Last Change:   09/15/2020 Job End Date:   11/02/2019
Appointment Status:   
Last Inspection By:   PORAZZO, P       On     09/15/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011334 Licensee Name: MICHAEL KATZ
Firm: 002750 Firm Name: A & M ELEC'L SERVICE INC.
Firm Phone: 718-668-1908  Firm Address: 516 INDUSTRIAL LOOP S.I NY 10309 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320597476
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54738     Submittal #: 17A0555  
Owner / Occup:
Owner Business Name: 420 KENT AVE LLC
Authorized Representative:  CHARLES MORISI
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  30A,100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  2  800A,1200A
E. Over 1200 AMPS  5  4000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  580  #2,#3,#8,#4
B. Over #2 to 1/0  36  #1/0,#1
C. Over 1/0 to 250 MCM  10  2/0,4/0,250,3/0
D. Over 250 MCM  87  750,500,350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  605  
C. 3 Phase Up to 225 AMPS  26  100A,200A
D. 3 Phase Over 225 AMPS  22  400A,800A,1200A,600A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    86  30    86  11  36  23  116     
001    1134  206    105  1134  10  675  30  120  500 
002    632  1560  38  398  632             
003    632  1560  38  398  632             
004    632  1560  38  398  632             
005    632  1560  38  398  632             
006    632  1560  38  398  632             
007    1094  172  19  134  1094  166  34     
008    274  879  28  186  274             
009    274  879  28  186  274             
010    274  879  28  186  274             
011    274  879  28  186  274             
012    274  879  28  186  274             
013    274  879  28  186  274             
014    274  879  28  186  274             
015    274  879  28  186  274             
016    274  879  28  186  274             
017    274  879  28  186  274             
018    274  879  28  186  274             
019    274  879  28  186  274             
020    274  879  28  186  274             
021    274  879  28  186  274             
022    274  879  28  186  274             
ROF    98  22    17  98  11  335  32     
ROF  EMR  11  15    11  185     
Buildings Total 9693  21430  629  5040  9693     1397     310     500 
Total Units : 48692 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/15/2017 Notice: 1 - FIRST NOTICE 08/24/2020
Power Issued: 11/15/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B437262
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/22/2020 08/24/2020 CLC V (275) (2)
INSPECTION COMMENTS: COMPLETE INSPECTION, FAILED
 
(2) 08/26/2020 08/26/2020 CLC J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000018584
 
(3) 09/15/2020 09/15/2020 PP1 C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000020775

OBJECTION FOR APPLICATION #: B437262
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) GYM FOUNTAIN NOT GFCI PROTECTED
RSLV 08/22/2020 08/22/2020 09/15/2020
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) SERVICE ENTRANCE RACEWAY BONDING UNDER 250.122
RSLV 08/22/2020 08/22/2020 08/26/2020