Electrical Application Details for App #: B436745
Premises: 488 4 AVENUE BROOKLYN BIN: 3022819     Block: 1021   Lot: 45
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 488 4TH AV Census Tract:   117 Health Area:  4300
CELLAR 1-10 ROOF Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
Related Job Number:    321177604
DOB Cross Street(s):    11 STREET,    12 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/03/2017 5:29 PM
Application Entered:   11/03/2017 Job Start Date:   11/03/2017
Last Change:   08/22/2025 Job End Date:   11/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     06/29/2022      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012312 Licensee Name: SAMUEL PALACE
Firm: 004091 Firm Name: DYNAMIC ELEC'L CONTRS INC
Firm Phone: 718-498-7476  Firm Address: 1046 WINTHROP STREET BROOKLYN NY 11212 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $1,014.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 10 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BALKANY LEVI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  10  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    35  50    20               
001    35  50    20               
002    35  50    20               
003    35  50    20               
004    35  50    20               
005    35  50    20               
006    35  50    20               
007    35  50    20               
008    35  50    20               
009    35  50    20               
010    35  50    20               
ROF    10  20      11  300         
Buildings Total 395  570    221       300           
Total Units : 1486 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/03/2017 Notice: 1 - FIRST NOTICE 06/29/2022
Power Issued: 11/03/2017 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B436745
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/29/2022 06/29/2022 MJD V (120) (20)
INSPECTION COMMENTS: FAIL. INSPECTION INCOMPLETE. COMMERCIAL SPACE AND APTS 2,3,4,5,6,7 NOT INSPECTED. ATOI JUDA.

OBJECTION FOR APPLICATION #: B436745
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (184) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(FLOOR: 001)ART 440.14 DISCONNECTS NOT PROVIDED FOR AIR HANDLERS FED FROM PANELON FIRST FLOOR.
OPEN 06/29/2022 06/29/2022
 
002 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 001)ART 210.52 LOWER LEVEL OF DUPLEX APT ON 1ST FL NOT PROVIDED WITHSUFFICIENT NUMBER OF RECEPTACLES.
OPEN 06/29/2022 06/29/2022
 
003 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 001)ART 210.52 RECEPTACLE NOT PROVIDED IN PERIMETER OF APT IN PORCH OF1ST FLOOR APT.
OPEN 06/29/2022 06/29/2022
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 008) ART 408.4 8TH FL PANEL NOT PROVIDED WITH DIRECTORY.
OPEN 06/29/2022 06/29/2022
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS)ART 110.3 ALL 15A RATED AIR HANDLERS OVERFUSED AS PER MANUFACTURERSSPECIFICATIONS.
OPEN 06/29/2022 06/29/2022
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ART 110.16 ARC FLASH LABELS NOT PROVIDED T-OUT.
OPEN 06/29/2022 06/29/2022
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) ART 314.20 NO BOX EXTENDERS PROVIDED T-OUT.
OPEN 06/29/2022 06/29/2022
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)ART 406.8 WR RECEPTACLES NOT PROVIDED FOR BOTH OUTDOOR BALCONIEST-OUT.
OPEN 06/29/2022 06/29/2022
 
009 (184) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(ALL FLOORS)ART 422.30 NO DISCONNECTS PROVIDED FOR 30A ELECTRIC OVENS T-OUTBUILDING.
OPEN 06/29/2022 06/29/2022
 
010 (247) SIMULTANEOUS OPENING OF POLES
(ALL FLOORS) ART 210.4 HANDLE TIES MISSING IN PANELS T-OUT BUILDING.
OPEN 06/29/2022 06/29/2022
 
011 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) ART 110.12 MISSING KOS IN PLP PANEL AND T-OUT BUILDING.
OPEN 06/29/2022 06/29/2022
 
012 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(ALL FLOORS)ART 210.52 NO RECEPTACLE PROVIDED BETWEEN SINK AND STOVE (OVER 2FTDISTANCE) IN APTS 10,9.
OPEN 06/29/2022 06/29/2022
 
013 (104) SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDING
(CELLAR)AM 230.43 COMMERCIAL PANEL SERVICE ENTRY CONDUCTORS RAN IN HOLLOWSPACE.
OPEN 06/29/2022 06/29/2022
 
014 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(CELLAR)ART 250.118 GROUND NOT PROVIDED BETWEEN FIRE PUMP CONTROLLER ANDFIRE PUMP.
OPEN 06/29/2022 06/29/2022
 
015 (154) THE OVERCURRENT DEVICE HAS NOT BEEN PROPERLY SIZED
(CELLAR)TABLE 310.16350MCM SERVICE ENTRANCE CONDUCTORS UNDERSIZED FOR 400APLP SERVICE DISCONNECT BREAKER.
OPEN 06/29/2022 06/29/2022
 
016 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) AM 230.70 SERVICE SWITCHES NOT PROPERLY IDENTIFIED.
OPEN 06/29/2022 06/29/2022
 
017 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) ART 250.102 400A SERVICE RACE WAYS NOT PROPERLY BONDED.
OPEN 06/29/2022 06/29/2022
 
018 (102) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) AM 110.2 INDOOR EXIT SIGNS USED OUTDOORS.
OPEN 06/29/2022 06/29/2022
 
019 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(ROOF)AM 330.12 PVC COATED MC CABLE USED IN RESIDENTIAL BUILDING ABOVE 3STORIES.
OPEN 06/29/2022 06/29/2022
 
020 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) ART 210.63 RECEPTACLE NOT PROVIDED FOR ROOF HVAC UNITS.
OPEN 06/29/2022 06/29/2022