| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
10 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(184) |
DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED (FLOOR: 001)ART 440.14 DISCONNECTS NOT PROVIDED FOR AIR HANDLERS FED FROM PANELON FIRST FLOOR. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 002 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 001)ART 210.52 LOWER LEVEL OF DUPLEX APT ON 1ST FL NOT PROVIDED WITHSUFFICIENT NUMBER OF RECEPTACLES. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 003 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 001)ART 210.52 RECEPTACLE NOT PROVIDED IN PERIMETER OF APT IN PORCH OF1ST FLOOR APT. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 004 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 008) ART 408.4 8TH FL PANEL NOT PROVIDED WITH DIRECTORY. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 005 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS)ART 110.3 ALL 15A RATED AIR HANDLERS OVERFUSED AS PER MANUFACTURERSSPECIFICATIONS. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 006 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ART 110.16 ARC FLASH LABELS NOT PROVIDED T-OUT. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ART 314.20 NO BOX EXTENDERS PROVIDED T-OUT. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 008 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)ART 406.8 WR RECEPTACLES NOT PROVIDED FOR BOTH OUTDOOR BALCONIEST-OUT. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 009 |
(184) |
DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED (ALL FLOORS)ART 422.30 NO DISCONNECTS PROVIDED FOR 30A ELECTRIC OVENS T-OUTBUILDING. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 010 |
(247) |
SIMULTANEOUS OPENING OF POLES (ALL FLOORS) ART 210.4 HANDLE TIES MISSING IN PANELS T-OUT BUILDING. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 011 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) ART 110.12 MISSING KOS IN PLP PANEL AND T-OUT BUILDING. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 012 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (ALL FLOORS)ART 210.52 NO RECEPTACLE PROVIDED BETWEEN SINK AND STOVE (OVER 2FTDISTANCE) IN APTS 10,9. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 013 |
(104) |
SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDING (CELLAR)AM 230.43 COMMERCIAL PANEL SERVICE ENTRY CONDUCTORS RAN IN HOLLOWSPACE. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 014 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (CELLAR)ART 250.118 GROUND NOT PROVIDED BETWEEN FIRE PUMP CONTROLLER ANDFIRE PUMP. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 015 |
(154) |
THE OVERCURRENT DEVICE HAS NOT BEEN PROPERLY SIZED (CELLAR)TABLE 310.16350MCM SERVICE ENTRANCE CONDUCTORS UNDERSIZED FOR 400APLP SERVICE DISCONNECT BREAKER. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 016 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) AM 230.70 SERVICE SWITCHES NOT PROPERLY IDENTIFIED. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 017 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) ART 250.102 400A SERVICE RACE WAYS NOT PROPERLY BONDED. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 018 |
(102) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF) AM 110.2 INDOOR EXIT SIGNS USED OUTDOORS. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 019 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (ROOF)AM 330.12 PVC COATED MC CABLE USED IN RESIDENTIAL BUILDING ABOVE 3STORIES. |
OPEN |
06/29/2022 |
06/29/2022 |
|
| |
| 020 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (ROOF) ART 210.63 RECEPTACLE NOT PROVIDED FOR ROOF HVAC UNITS. |
OPEN |
06/29/2022 |
06/29/2022 |
|