BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B436241
Premises: 5400 AVENUE U BROOKLYN BIN: 3326830     Block: 8470   Lot: 55
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 5100 KINGS PLAZA Census Tract:   698 Health Area:  8822
1ST FLOOR - 4TH FLOOR INFRASTR Admin Area:   B - BROOKLYN Inspection Area:   Q
BROOKLYN, NY 11234 Community Board:   318
Special Place Name:   KINGS PLAZA MALL
DOB Cross Street(s):   FLATBUSH AVENUE,    EAST 52 STREET
Status:   C - JOB IS SIGNED OFF 08/23/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/25/2017 3:12 PM
Application Entered:   10/25/2017 Job Start Date:   10/25/2017
Last Change:   08/23/2018 Job End Date:   07/18/2018
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     08/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011456 Licensee Name: RALPH OCCHIPINTI
Firm: 000064 Firm Name: ADCO ELEC'L CORP
Firm Phone: 718-494-4400  Firm Address: 201 EDWARD CURRY AVENUE STATEN ISLAND NY 10314 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $3,105.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  321373580
Building Used As:   Z - Other
Store / Other:   MALL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER MULHALL
Owner Business Name: AURORA CONTRACTORS
Authorized Representative:  ANTHONY VERO
Relationship To Owner:   CONSTRUCTION MANGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  12  VARIOUS
B. Over #2 to 1/0  9  VARIOUS
C. Over 1/0 to 250 MCM  2  INCL MECHANICAL EQ FEEDS
D. Over 250 MCM  8  VARIOUS SEE DRAWINGS
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  10  
D. 3 Phase Over 225 AMPS  5  400 AMPS / EM PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
EPT                 
GND    280  60    250  416  12  36  300 
OSP        200     
LOB    52    12  52             
002    190  24    100  190  24  150 
003    232  36    48  232          150 
004    358  42    250  358             
ROF    12    12  24  80         
Buildings Total 1130  189    676  1268     288     62     600 
Total Units : 4213 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/21/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB 170009 GIA NEW RETAIL FIT OUT INFRASTRUCTURE WORK, INCLUDES FEEDERS BRANCH POWER TO SIGN JUNCTION BOXES POWER TO ELEVATOR / ESCALATOR MOTORS MAIN DISTRIBUTION AND GENERATOR FEEDERS ASSOCIATED WITH ADVISORY BOARD APPROVAL PENDING TO FOLLOW

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B436241
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/20/2018 06/21/2018 NJP V (300) (5)
INSPECTION COMMENTS: CORRECT OBJECTIONS. MOTORS & HEATERS ON APP WAS NOT INSPECTED. TRANSFORMER/PANELS AND GENERAL WIRING WAS INSPECTED.
 
(2) 08/09/2018 08/10/2018 EID C R (160) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED. JOB IS OK

OBJECTION FOR APPLICATION #: B436241
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001)1ST FLR HALLWAY DISCONNECT SWITCH/PANEL NOT IDENTIFIED. (ART 110.22)
RSLV 06/20/2018 06/20/2018 08/09/2018
 
002 (999) OTHER
(FLOOR: 001)1ST FLR SOUTH SIDE HALLWAY PANEL NOT IDENTIFIED (ART 110.22)
RSLV 06/20/2018 06/20/2018 08/09/2018
 
003 (260) SIGNAGE NOT PROVIDED FOR SERVICE ROOM
(FLOOR: 004) SIGNAGE FOR SVC ROOM NOT PROVIDED. (AMEND 110.25)
RSLV 06/20/2018 06/20/2018 08/09/2018
 
004 (999) OTHER
(FLOOR: 004) SVC SWITCH PLAQUE NOT PROVIDED FOR RP6B1A (ART 230.2E)
RSLV 06/20/2018 06/20/2018 08/09/2018
 
005 (999) OTHER
(ALL FLOORS)THROUGHOUT TRANSFORMERS ARE NOT IDENTIFIED. (ART 110.22)
RSLV 06/20/2018 06/20/2018 08/09/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.