Electrical Application Details for App #: B436067
Premises: 135 EASTERN PARKWAY BROOKLYN BIN: 3029628     Block: 1179   Lot: 47
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 135 EASTERN PARKWAY Census Tract:   215 Health Area:  2720
5TH FLOOR APT 5G Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   UNDERHILL AVENUE,    WASHINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 01/23/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/23/2017 8:16 AM
Application Entered:   10/23/2017 Job Start Date:   10/23/2017
Last Change:   01/23/2018 Job End Date:   10/22/2018
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     12/19/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010069 Licensee Name: PETER AMABILE
Firm: 003346 Firm Name: FLEMINGTON ELEC'L MAINT I
Firm Phone: 646-230-9903  Firm Address: 225 31 STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $43.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LAWRENCE ROTH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  5G  10               
Buildings Total 10                  
Total Units : 24 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/19/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  KITCHEN RENOVATION. APPLIANCE AND COUNTERTOP LOCATIONS BEING RELOCATED WORK TO BE DONE ONLY IN KITCHEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B436067
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2017 12/19/2017 OSZ V (30) (3)
INSPECTION COMMENTS: CORRECT OBJECTIONS.
 
(2) 12/19/2017 12/20/2017 DIT C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B436067
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 005) KITCHEN RECEPTACLES NOT PROPERLY GROUNDED. ART. 250.146
RSLV 12/19/2017 12/19/2017 12/19/2017
 
002 (999) OTHER
(FLOOR: 005)SETBACK ON KITCHEN COUNTERTOP GFCI RECEPTACLES. ART. 314.20
RSLV 12/19/2017 12/19/2017 12/19/2017
 
003 (999) OTHER
(FLOOR: 005)SETBACK ON MICROWAVE RECEPTACLE IN CABINET OVER STOVE. ART 314.20
RSLV 12/19/2017 12/19/2017 12/19/2017