Electrical Application Details for App #: B436007
Premises: 1365 DE KALB AVENUE BROOKLYN BIN: 3073542     Block: 3234   Lot: 47
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1365 DEKALB AV. Census Tract:   423 Health Area:  3200
APT. 3R Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11221 Community Board:   304
DOB Cross Street(s):   CENTRAL AVENUE,    WILSON AVENUE
Status:   C - JOB IS SIGNED OFF 08/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/20/2017 8:59 AM
Application Entered:   10/20/2017 Job Start Date:   10/20/2017
Last Change:   08/08/2018 Job End Date:   10/10/2018
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     03/08/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012276 Licensee Name: ORLANDO D TORRES
Firm: 004033 Firm Name: O.K. ELEC'L SERVICE CORP
Firm Phone: 718-652-1212  Firm Address: 727A BURKE AVENUE BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $90.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN BRENNAN
Owner Business Name: LACEY LLC
Authorized Representative:  JOHN BRENNAN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1- 100 AMPS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3R  25  30  10  25             
Buildings Total 25  30  10  25                
Total Units : 93 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/29/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING, RISER AND PANEL FOR APARTMENT 3R ONLY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B436007
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2018 01/29/2018 JGX V (48) (10)
INSPECTION COMMENTS: OBJECTIONS ISSUED.
 
(2) 03/08/2018 03/08/2018 CJE C R (40) (0)
INSPECTION COMMENTS: ALL OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B436007
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 003)OVERCURRENT PROTECTION FOR WASHER IS NOT PROPER SIZE. ART. 240.3
RSLV 01/26/2018 01/26/2018 03/08/2018
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 003)OVERCURRENT PROTECTION FOR DRYER IS NOT PROPER SIZE. ART. 240.3
RSLV 01/26/2018 01/26/2018 03/08/2018
 
003 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 003)ARMORED CABLES TERMINATER WITHOUT ANTISHORT BUSHINGS. ART. 320.40
RSLV 01/26/2018 01/26/2018 03/08/2018
 
004 (999) OTHER
(FLOOR: 003)MICROWAVE RECEP BOX NOT FLUSH WITH WOOD PANEL. ART 314.20
RSLV 01/26/2018 01/26/2018 03/08/2018
 
005 (999) OTHER
(FLOOR: 003)SETBACK AT COUNTERTOP RECEPS IS MORE THAN 1/4 INCH. ART. 314.20
RSLV 01/26/2018 01/26/2018 03/08/2018
 
006 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 003)OVERCURRENT PROTECTION FOR DRYER IS NOT PROPER SIZE. ART. 240.3
RSLV 01/26/2018 01/26/2018 03/08/2018
 
007 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 003)OVERCURRENT PROTECTION FOR WASHER IS NOT PROPER SIZE. ART. 240.3
RSLV 01/26/2018 01/26/2018 03/08/2018
 
008 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 003)ARMORED CABLES TERMINATER WITHOUT ANTISHORT BUSHINGS. ART. 320.40
RSLV 01/26/2018 01/26/2018 03/08/2018
 
009 (999) OTHER
(FLOOR: 003)MICROWAVE RECEP BOX NOT FLUSH WITH WOOD PANEL. ART 314.20
RSLV 01/26/2018 01/26/2018 03/08/2018
 
010 (999) OTHER
(FLOOR: 003)SETBACK AT COUNTERTOP RECEPS IS MORE THAN 1/4 INCH. ART. 314.20
RSLV 01/26/2018 01/26/2018 03/08/2018