Electrical Application Details for App #: B435838
Premises: 237 DUFFIELD STREET BROOKLYN BIN: 3425660     Block: 146   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 237 DUFFIELD ST Census Tract:   15
SUB CELLAR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320915649
DOB Cross Street(s):   WILLOUGHBY STREET,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 03/20/2023
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/17/2017 Job Start Date:   10/02/2017
Last Change:   03/20/2023 Job End Date:   11/20/2017
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     03/20/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011225 Licensee Name: ZVI GELB
Firm: 002626 Firm Name: ZEREM ELECTRIC CORP.
Firm Phone: 718-377-8685  Firm Address: 3011 AVENUE L BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,975.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54759     Submittal #: 17A0450  
Owner / Occup:
Owner Business Name: DANYA CEBUS
Authorized Representative:  GIDEON MAGEN
Relationship To Owner:   PROJECT EXECUTIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  2-400 A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-2000A, 1-1600A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  13  2-600MCM, 11-500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 110 #4-Wire 0 #10-Wire 4
Existing Meters 0 + New Meters 114 - Removed Meters 0 = Total Meters 114

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/17/2017 Notice: 1 - FIRST NOTICE 03/05/2019
Power Issued: 10/17/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FILING FOR ADVISORY BOARD SERVICE ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B435838
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/03/2018 10/04/2018 NJP N (35) (0) Y
INSPECTION COMMENTS: CONTRACTOR WAS NO SHOW AND UNAWARE OF INSPECTION "WILL RESCHEDULE".
 
(2) 03/04/2019 03/05/2019 EID V (205) (16)
INSPECTION COMMENTS: SVC ONLY COVERED BY THIS APP. GENERATOR NOT INSPECTED. ALL OTHER INSPECTED. OBJ ISSUED.
 
(3) 03/20/2023 03/20/2023 DIT C R (122) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B435838
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS)FROM CEL TO SUB: SVC RACEWAYS FROM SEB TO MAIN INCOMING SVC ENT.CABINET NOT BONDED.
RSLV 03/04/2019 03/04/2019 03/20/2023
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)FIRE RATED ROOM NOT BUILT AROUND CU DETAILED SEB AS ILLUSTRATED ONDRAWINGS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ROOF) GENERATOR: NO GEC PROVIDED TO GEN.
RSLV 03/04/2019 03/04/2019 03/20/2023
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(SUB-CELLAR)TROUGH ON LINE SIDE OF FP SVC SW NOT PROPERLY BND TO SVC SW ENCL.
RSLV 03/04/2019 03/04/2019 03/20/2023
 
005 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR) ROOM LAYOUT NOT SAME AS INDICATED ON DRAWING
RSLV 03/04/2019 03/04/2019 03/20/2023
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)FP. RM.: CONDUCTORS FROM CONTROLLER TO MTR NOT SIZED AS INDICATED ONDRAWINGS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
007 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: FP LOAD SIDE FEEDERS NOT ENCASED IN CONCRETE AS INDICATEDON DRAWING
RSLV 03/04/2019 03/04/2019 03/20/2023
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: FA LOAD SIDE COND. NOT #4 AS INDICATED ON DRAWING
RSLV 03/04/2019 03/04/2019 03/20/2023
 
009 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: FA SVC TAP NOT INSTALLED AS INDICATED ON DRAWINGS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
010 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: GEC TO "MSB" NOT TERM. AT NEUTRAL AS INDICATED ON DWG.
RSLV 03/04/2019 03/04/2019 03/20/2023
 
011 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: SUPP. GND COND. NOT TERMINATED AT COLLECTOR BAR
RSLV 03/04/2019 03/04/2019 03/20/2023
 
012 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM: BARRIER NOT INSTALLED AT OPEN ENDS BEHIND CABINETS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
013 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM: COLLECTOR BUS AND FA SVC SW NOT INSTALLED IN LOCATIONSSPECIFIED ON DRAWINGS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
014 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: COLLECTOR BUS NOT SAME SIZE AS INDICATED ON DRAWINGS
RSLV 03/04/2019 03/04/2019 03/20/2023
 
015 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)ELEC. RM.: MECHANICAL VENTILATION NOT PROVIDED FOR ELECTRIC ROOM
RSLV 03/04/2019 03/04/2019 03/20/2023
 
016 (999) OTHER
(SUB-CELLAR) ELEC. RM.: SVC SWS ARE NOT MARKED AS SVC (ART. 230.70)
RSLV 03/04/2019 03/04/2019 03/20/2023