| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
2-400 A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
2 |
1-2000A, 1-1600A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
13 |
2-600MCM, 11-500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (ALL FLOORS)FROM CEL TO SUB: SVC RACEWAYS FROM SEB TO MAIN INCOMING SVC ENT.CABINET NOT BONDED. |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)FIRE RATED ROOM NOT BUILT AROUND CU DETAILED SEB AS ILLUSTRATED ONDRAWINGS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 003 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (ROOF) GENERATOR: NO GEC PROVIDED TO GEN. |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 004 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (SUB-CELLAR)TROUGH ON LINE SIDE OF FP SVC SW NOT PROPERLY BND TO SVC SW ENCL. |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 005 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR) ROOM LAYOUT NOT SAME AS INDICATED ON DRAWING |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)FP. RM.: CONDUCTORS FROM CONTROLLER TO MTR NOT SIZED AS INDICATED ONDRAWINGS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: FP LOAD SIDE FEEDERS NOT ENCASED IN CONCRETE AS INDICATEDON DRAWING |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: FA LOAD SIDE COND. NOT #4 AS INDICATED ON DRAWING |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: FA SVC TAP NOT INSTALLED AS INDICATED ON DRAWINGS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: GEC TO "MSB" NOT TERM. AT NEUTRAL AS INDICATED ON DWG. |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: SUPP. GND COND. NOT TERMINATED AT COLLECTOR BAR |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM: BARRIER NOT INSTALLED AT OPEN ENDS BEHIND CABINETS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM: COLLECTOR BUS AND FA SVC SW NOT INSTALLED IN LOCATIONSSPECIFIED ON DRAWINGS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: COLLECTOR BUS NOT SAME SIZE AS INDICATED ON DRAWINGS |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 015 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)ELEC. RM.: MECHANICAL VENTILATION NOT PROVIDED FOR ELECTRIC ROOM |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |
| |
| 016 |
(999) |
OTHER (SUB-CELLAR) ELEC. RM.: SVC SWS ARE NOT MARKED AS SVC (ART. 230.70) |
RSLV |
03/04/2019 |
03/04/2019 |
03/20/2023 |