BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B434970
Premises: 63 FLUSHING AVENUE BROOKLYN BIN: 3335129     Block: 2023   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 63 FLUSHING AV Census Tract:   543 Health Area:  9300
GROUND Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11205 Community Board:   302
DOB Cross Street(s):   NORTH OXFORD STREET,    CUMBERLAND STREET
Status:   C - JOB IS SIGNED OFF 12/11/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/27/2017 11:45 AM
Application Entered:   09/27/2017 Job Start Date:   09/27/2017
Last Change:   12/11/2018 Job End Date:   09/27/2018
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     12/07/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009615 Licensee Name: ROBERT COVELLO
Firm: 001205 Firm Name: ROBERT S. COVELLO
Firm Phone: 718-786-7390  Firm Address: 51-20 35TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE ZICCARDI
Owner Business Name: Z CAR D CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                   
Buildings Total                   
Total Units : 12 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/26/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FILING FOR FOUR FEEDS FOR FOUR SIGNS (4) SWITCHES (4) OUTLETS FOR FIXTURES. ONE SIGN SAYS BROOKLYN NAVY YARD TWO SIGNS ARE BUILDING NUMBERS "77" AND THE LAST ONE IS A MULTI TENENT DIRECTORY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B434970
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/26/2018 11/26/2018 JGX V (65) (3)
INSPECTION COMMENTS: INSPECTION COMPLETED. 3 # OBJECTIONS ISSUED. 277V EQPMNT TO BE MARKED.
 
(2) 12/07/2018 12/07/2018 EID C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED. INSPECTION COMPLETED. PASS

OBJECTION FOR APPLICATION #: B434970
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002) SPLICING NOT SECURE AT DRIVER ENCLOSURES. ART. 110.14 B
RSLV 11/26/2018 11/26/2018 12/07/2018
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(FLOOR: 002) EMT NOT SUPPORTED NEAR CONTROLLERS. ART. 358.30
RSLV 11/26/2018 11/26/2018 12/07/2018
 
003 (999) OTHER
(FLOOR: 002)SELF-TAPPING SCREWS USED AT DRIVER ENCLOSURES. ART. 110.3 B
RSLV 11/26/2018 11/26/2018 12/07/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order