BIS Menu  |  Print Electrical Permit  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B434697
Premises: 383 STATE STREET BROOKLYN BIN: 3000567     Block: 172   Lot: 55
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 383 STATE ST Census Tract:   41 Health Area:  2400
SIDE WALK Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
DOB Cross Street(s):   BOND STREET,    NEVINS STREET
Status:   C - JOB IS SIGNED OFF 09/24/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/21/2017 1:00 PM
Application Entered:   09/21/2017 Job Start Date:   09/21/2017
Last Change:   09/24/2019 Job End Date:   09/21/2018
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     09/24/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011683 Licensee Name: SILVANO TRAVALJA
Firm: 003348 Firm Name: SAMCO ELECTRIC CORP.
Firm Phone: 718-204-2433  Firm Address: 37-35 9TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $41.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYCSCA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 16 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 09/23/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PS 369K - SHED LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B434697
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/04/2019 09/04/2019 JGX V (19) (1)
INSPECTION COMMENTS: UNABLE TO VERIFY GFCI PROTECTION FOR BRANCH CKT/S. 1 OBJECTION ISSUED.
 
(2) 09/23/2019 09/23/2019 JGX V X (21) (2)
INSPECTION COMMENTS: 2 NEW OBJECTIONS ISSUED.
 
(3) 09/24/2019 09/24/2019 CJH C R (33) (0)
INSPECTION COMMENTS: REFER TO B00102565

OBJECTION FOR APPLICATION #: B434697
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(GROUND FLOOR) CONDUIT SUPPORT STRAPS LOOSE. ART. 342.30
RSLV 09/04/2019 09/04/2019 09/24/2019
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(GROUND FLOOR)BONDING JUMPER MISSING BETWEEN SECTIONS OF SHED. ART. 250.4.A.4
RSLV 09/23/2019 09/23/2019 09/24/2019
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(GROUND FLOOR) SECTIONS OF SHED SUPPORT NOT GROUNDED. ART. 250.4.A.2
RSLV 09/23/2019 09/23/2019 09/24/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Print Electrical Permit  |  Electrical Inspection Work Order  |  Back