BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B434496
Premises: 135 COFFEY STREET BROOKLYN BIN: 3397387     Block: 597   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 135 COFFEY ST Census Tract:   53 Health Area:  4100
ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
DOB Cross Street(s):   VAN BRUNT STREET,    CONOVER STREET
Status:   C - JOB IS SIGNED OFF 03/06/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/19/2017 8:02 AM
Application Entered:   09/19/2017 Job Start Date:   09/19/2017
Last Change:   03/06/2019 Job End Date:   12/15/2017
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     03/01/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $878.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSAN FRIEDLAND
Owner Business Name: FIFTH AVE COMMITTEE
Authorized Representative:  SUSAN FRIEDLAND
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  5  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF            200         
Buildings Total            200           
Total Units : 201 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 20 #4-Wire 1 #10-Wire 0
Existing Meters 21 + New Meters 21 - Removed Meters 21 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/19/2017 Notice: 1 - FIRST NOTICE 02/09/2019
Power Issued: 09/19/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B434496
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/2019 02/09/2019 CJH V (72) (7)
INSPECTION COMMENTS: TRANSFER SWITCHES NOT INSPECTED, STILL BEEN WORK ON. PROPERTY LINE BOX NOT INSPECTED
 
(2) 02/16/2019 02/19/2019 NJP N (15) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(3) 03/01/2019 03/02/2019 NJP C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: B434496
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) GND FL SVC SWITCHES PLAQUES NOT PROVIDED 230.2
RSLV 02/09/2019 02/09/2019 03/01/2019
 
002 (999) OTHER
(GROUND FLOOR) GND FL PANELS NOT LABEL IN TRANSFER ROOM 408.4
RSLV 02/09/2019 02/09/2019 03/01/2019
 
003 (999) OTHER
(GROUND FLOOR)GND FL SVC ROOM FEEDERS CONDUCTORS COMPARTMENT GND BAR SELF TAPSCREWS IN USED 250.8
RSLV 02/09/2019 02/09/2019 03/01/2019
 
004 (999) OTHER
(GROUND FLOOR) GND FL PNL KO MISSING 110.2
RSLV 02/09/2019 02/09/2019 03/01/2019
 
005 (999) OTHER
(GROUND FLOOR) GND FL PNL GND CONDUCTOR NOT TERMINATED 250.112
RSLV 02/09/2019 02/09/2019 03/01/2019
 
006 (999) OTHER
(GROUND FLOOR)GND FL TO ROOF EMERGENCY RACE WAY BOXES AND EQUIPMENT NOT MARK 700.9
RSLV 02/09/2019 02/09/2019 03/01/2019
 
007 (999) OTHER
(GROUND FLOOR) GND FL PNL CKT NOT GROUPED 210.4D
RSLV 02/09/2019 02/09/2019 03/01/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order