BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B434317
Premises: 63 FLUSHING AVENUE BROOKLYN BIN: 3335129     Block: 2023   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 63 FLUSHING AV Census Tract:   543 Health Area:  9300
5TBUILDING #77 ROOM # 509/5.16 Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11205 Community Board:   302
DOB Cross Street(s):   NORTH OXFORD STREET,    CUMBERLAND STREET
Status:   C - JOB IS SIGNED OFF 01/04/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/14/2017 12:18 PM
Application Entered:   09/14/2017 Job Start Date:   09/14/2017
Last Change:   01/04/2018 Job End Date:   09/13/2018
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     11/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012628 Licensee Name: KOSTANDIN RRAPO
Firm: 004463 Firm Name: TRANSFORM ELECTL CONTRS I
Firm Phone: 212-686-8788  Firm Address: 32 EAST 31ST STREET, 8TH FL NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $43.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: CARE/OF
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  509    22                   
Buildings Total   22                      
Total Units : 22 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B434317
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/23/2017 10/23/2017 DAH J (35) (1)
INSPECTION COMMENTS: THE CONTRACTOR SAID HE'LL INSTALL THE GFCI THAT IS MISSING
 
(2) 11/13/2017 11/15/2017 NJP C R (35) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED.

OBJECTION FOR APPLICATION #: B434317
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 005) ADJACENT TO SINK
RSLV 10/23/2017 10/23/2017 11/13/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order