| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200 AMPS |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
4/3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
12/24 |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001) (ART. 240.3) OCP AC (20A) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001) (ART. 300.13) NEUTRAL NOT SPLICED (KITCHEN 12/3 BX) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 003 |
(999) |
OTHER (FLOOR: 002) (ART. 210.7(B)) MULTICIRCUIT (PANEL) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) (ART. 410.16(B)) CLOSET LIGHT (ALL FLOORS) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) (ART. 210.4(D)) GROPING (ALL PANELS) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 006 |
(999) |
OTHER (BASEMENT)(ART. 250.66) GROUND CONDUCTOR IMPROPER SIZE (WATER METER JUMPER ANDMIGB JUMPER) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 007 |
(999) |
OTHER (BASEMENT) (ART. 250.8(A)) SCREW FOR GROUND LUG |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 008 |
(999) |
OTHER (OPEN SPACE) (ART. 210.52(E1) FRONT OUTLET |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 009 |
(999) |
OTHER (OPEN SPACE) (ART. 210.70(A2)) ENTER LIGHT (BACKYARD AND FRONT) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 010 |
(999) |
OTHER (OPEN SPACE) (ART. 320.40) NO FITTING FOR BX (BOTH SPLICE BOXES) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |
| |
| 011 |
(999) |
OTHER (OPEN SPACE)(ART. 250.119(A2)) IDENTIFICATION FOR EGC (BOTH SPLICE BOXES) |
RSLV |
06/06/2018 |
06/06/2018 |
06/19/2018 |