Electrical Application Details for App #: B433074
Premises: 292 12 STREET BROOKLYN BIN: 3337713     Block: 1029   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 292 12 ST Census Tract:   139 Health Area:  4600
BSMT THROUGHOUT Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
Related Job Number:    321570340
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 06/19/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/17/2017 12:15 PM
Application Entered:   08/17/2017 Job Start Date:   08/17/2017
Last Change:   06/19/2018 Job End Date:   10/16/2017
Appointment Status:   
Last Inspection By:   SERGIY MOTORIN       On     06/19/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $215.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TODD S SPODEK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12/24
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL               
GND    27  25    10  27         
001    25  25    10  25             
002    25  25    10  25             
Buildings Total 85  83  33  85              
Total Units : 292 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 1 - Removed Meters 2 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/17/2017 Notice: 1 - FIRST NOTICE 06/06/2018
Power Issued: 08/17/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONVERSION TWO FAMILY TO ONE FAMILY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B433074
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2018 06/06/2018 SGY V (50) (11)
INSPECTION COMMENTS: OBJECTIONS ISSUED.
 
(2) 06/19/2018 06/19/2018 SGY C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS (11) RESOLVED.

OBJECTION FOR APPLICATION #: B433074
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) (ART. 240.3) OCP AC (20A)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
002 (999) OTHER
(FLOOR: 001) (ART. 300.13) NEUTRAL NOT SPLICED (KITCHEN 12/3 BX)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
003 (999) OTHER
(FLOOR: 002) (ART. 210.7(B)) MULTICIRCUIT (PANEL)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
004 (999) OTHER
(ALL FLOORS) (ART. 410.16(B)) CLOSET LIGHT (ALL FLOORS)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
005 (999) OTHER
(ALL FLOORS) (ART. 210.4(D)) GROPING (ALL PANELS)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
006 (999) OTHER
(BASEMENT)(ART. 250.66) GROUND CONDUCTOR IMPROPER SIZE (WATER METER JUMPER ANDMIGB JUMPER)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
007 (999) OTHER
(BASEMENT) (ART. 250.8(A)) SCREW FOR GROUND LUG
RSLV 06/06/2018 06/06/2018 06/19/2018
 
008 (999) OTHER
(OPEN SPACE) (ART. 210.52(E1) FRONT OUTLET
RSLV 06/06/2018 06/06/2018 06/19/2018
 
009 (999) OTHER
(OPEN SPACE) (ART. 210.70(A2)) ENTER LIGHT (BACKYARD AND FRONT)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
010 (999) OTHER
(OPEN SPACE) (ART. 320.40) NO FITTING FOR BX (BOTH SPLICE BOXES)
RSLV 06/06/2018 06/06/2018 06/19/2018
 
011 (999) OTHER
(OPEN SPACE)(ART. 250.119(A2)) IDENTIFICATION FOR EGC (BOTH SPLICE BOXES)
RSLV 06/06/2018 06/06/2018 06/19/2018