BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B431064
Premises: 354 14 STREET BROOKLYN BIN: 3023762     Block: 1043   Lot: 29
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 354 14TH ST Census Tract:   149 Health Area:  4700
2ND & 3RD FLOOR Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    6 AVENUE,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 06/12/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/07/2017 7:50 AM
Application Entered:   07/07/2017 Job Start Date:   07/07/2017
Last Change:   06/12/2018 Job End Date:   07/02/2018
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     06/11/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011047 Licensee Name: ANTHONY CIRRINCIONE
Firm: 004444 Firm Name: EMCO ELECTRIC SVCS LLC
Firm Phone: 212-420-9766  Firm Address: 526 WEST 26TH ST.,STE1012 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $167.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTINA HOWELL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  30/30
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  25  37    17  25             
003  29  39    18  29             
Buildings Total 54  76    35  54                
Total Units : 219 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/17/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING AND NEW CIRCUIT INSTALLATION. INSTALLATION OF 3 SPLIT A/C UNITS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B431064
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/16/2018 05/17/2018 NJP V (40) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED. AC UNITS NOT INSPECTED DUE TO THE WEATHER APARTMENT.
 
(2) 06/11/2018 06/12/2018 NJP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: B431064
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 003) PANEL DIRECTORY INCOMPLETE .(ART 408.4)
RSLV 05/16/2018 05/16/2018 06/11/2018
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) THROUGHOUT LIGHTS NOT PROPERLY GROUNDED (ART 250.4)
RSLV 05/16/2018 05/16/2018 06/11/2018
 
003 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(ALL FLOORS)BATHROOM FIXTURE NOT SUITABLE FOR DAMP OR WET LOCATION. (ART 410.10)
RSLV 05/16/2018 05/16/2018 06/11/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.