NYC Department of Buildings
Electrical Application Details for App #: B429836
Premises: 382 A MONROE STREET BROOKLYN BIN: 3051485     Block: 1820   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 382A MONROE ST Census Tract:   265 Health Area:  2000
CELLAR, BSEMT, 1, 2, 3, ROOF Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11221 Community Board:   303
DOB Cross Street(s):   TOMPKINS AVENUE,    THROOP AVENUE
Status:   C - JOB IS SIGNED OFF 03/23/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/08/2017 11:54 PM
Application Entered:   06/08/2017 Job Start Date:   06/09/2017
Last Change:   03/23/2018 Job End Date:   04/12/2018
Appointment Status:   
Last Inspection By:   JEROME BLACK       On     03/01/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012002 Licensee Name: MICHAEL S SARDO
Firm: 003672 Firm Name: AMR ELEC'L CONTRG CORP
Firm Phone: 718-902-2263  Firm Address: 1521 A BOONE AVENUE BRONX NY 10460 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $82.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: THOMAS DEVITO
Owner Business Name: WHITEROCK VENTURES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
BAS    16               
001    18    17             
002    17    12             
003    17    14             
ROF                     
Buildings Total 25  73    27  53              
Total Units : 180 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 3 - Removed Meters 4 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/08/2017 Notice: 1 - FIRST NOTICE 02/16/2018
Power Issued: 06/08/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW WIRING FOR LIGHT AND POWER AND NEW ELECTRIC PANELS AND METER PANS. 3 FAMILY BEING CONVERTED TO 2 FAMILY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B429836
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/15/2018 02/16/2018 JGX V (60) (9)
INSPECTION COMMENTS: SEE OBJECTIONS. ROOF, BALCONIES, A/C SYSTEMS AND EXTERNAL GFCI'S NOT INSPECTED. CHECK FOR EXTERNAL GFCI'S.
 
(2) 03/01/2018 03/01/2018 JKJ C R (35) (0)
INSPECTION COMMENTS: THIS JOB IS GOOD OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: B429836
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) WALL RECEPTACLES NEED GFCI PROTECTION
RSLV 02/15/2018 02/15/2018 03/01/2018
 
002 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(ALL FLOORS)PANELS FLRS 1, 2 AND 3 - SERVICE SWITCH NEUTRAL NOT BONDED. ART250.28
RSLV 02/15/2018 02/15/2018 03/01/2018
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS)PANEL HAS NO DIRECTORY / DIRECTORY INACCURATE. ART. 408.4
RSLV 02/15/2018 02/15/2018 03/01/2018
 
004 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(BASEMENT) DEFECTIVE GFCI AT COUNTERTOP AND BTH RM.
RSLV 02/15/2018 02/15/2018 03/01/2018
 
005 (999) OTHER
(BASEMENT) NO SIMULTANEOUS TRIP.
RSLV 02/15/2018 02/15/2018 03/01/2018
 
006 (999) OTHER
(BASEMENT) NO GFCI AT FRONT OF BLDNG.
RSLV 02/15/2018 02/15/2018 03/01/2018
 
007 (999) OTHER
(BASEMENT) SETBACK AT COUNTERTOP RECEPTACLES. ART 314.20
RSLV 02/15/2018 02/15/2018 03/01/2018
 
008 (999) OTHER
(CELLAR) NO LIGHTING IN STAIRWAY TO YARD.
RSLV 02/15/2018 02/15/2018 03/01/2018
 
009 (999) OTHER
(CELLAR) MAIN BRKR NOT SECURED.
RSLV 02/15/2018 02/15/2018 03/01/2018