| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
3/0 200AMP |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
200AMP |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 001) (ART. 424.19) SWITCH FOR FIREPLACE |
RSLV |
12/13/2018 |
12/13/2018 |
02/25/2019 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001) (ART. 314.20) SET BACK (KITCHEN) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 003 |
(999) |
OTHER (FLOOR: 001) (ART. 250.122) SIZE EGC FOR OVEN |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)(ART. 210.12(B)) LIVING SPACE NOT FULLY AFCI PROTECTED (ALL FLOORS) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) (ART. 408.4) DIRECTION (ALL PANELS) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) (ART. 410.16(B)) CLOSET LIGHTING (ALL FLOORS) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 007 |
(999) |
OTHER (BASEMENT) (ART. 250.8(A)) SCREW FOR GROUND BAR (SUBPANEL) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 008 |
(999) |
OTHER (BASEMENT) (ART. 210.7(B)) MULTICIRCUIT (SUBPANEL) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 009 |
(999) |
OTHER (BASEMENT) (ART. 250.52(A)) WATER MAIN GC CONNECTION |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 010 |
(999) |
OTHER (BASEMENT) (ART. 250.24(A)) NEUTRAL BONDED LOAD SIDE (SUBPANEL) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 011 |
(999) |
OTHER (BASEMENT) (ART. 320.15) BX NOT SUPPORTED (CEILING) |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 012 |
(999) |
OTHER (BASEMENT) (ART. 210.52(G)) BASEMENT RECEPTACLES NOT GFCI PROTECTED |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 013 |
(999) |
OTHER (OPEN SPACE) (ART. 406.8(B)) WR FOR OUTSIDE |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |
| |
| 014 |
(999) |
OTHER (OPEN SPACE) (ART. 210.52(E1)) FRONT OUTLET |
RSLV |
12/13/2018 |
12/13/2018 |
01/10/2019 |