BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B429010
Premises: 52 PLAZA STREET BROOKLYN BIN: 3029333     Block: 1171   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 60 PLAZA ST E Census Tract:   207 Health Area:  4500
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   BUTLER PLACE,    ST JOHNS PLACE
Status:   C - JOB IS SIGNED OFF 09/12/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/22/2017 12:32 PM
Application Entered:   05/22/2017 Job Start Date:   05/22/2017
Last Change:   09/12/2017 Job End Date:   04/22/2018
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     08/29/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011316 Licensee Name: RALPH J RUSSO
Firm: 002733 Firm Name: RJ RUSSO ELECTRIC CO.
Firm Phone: 718-423-4742  Firm Address: 45-57 BELL BLVD BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $100.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RONNIE MANDLER
Owner Business Name: 60 PLAZA OWNERS CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  2-200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/22/2017 Notice: 1 - FIRST NOTICE 07/13/2017
Power Issued: 05/22/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 2 NEW METERPANS FOR PLP METERS AND 2 NEW MAIN DISCONNECTS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B429010
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/20/2017 06/22/2017 FDY J (17) (0) Y
INSPECTION COMMENTS: JOB NOT READY FOR INSPECTION.
 
(2) 07/13/2017 07/13/2017 CJE V (20) (4)
INSPECTION COMMENTS: INSPECTION FAIL.
 
(3) 07/31/2017 07/31/2017 FWE J R (1) (0)
INSPECTION COMMENTS: METERS ARE READY TO ENERGIZE.OK FOR CON ED TO SET METERS. THE OTHER PART TO BE REINSERTED. .NPI JOB IN PROGRESS.
 
(4) 07/21/2017 08/09/2017 FDY J (58) (0) Y
INSPECTION COMMENTS: THE METERS ARE READY TO BE ENERGIZED BY CON ED. A FULL INSPECTION OF ALL EQUIPMENT INCLUDING SOLAR INSTALLATIONS WILL BE REQUIRED AFTER THE METERS ARE ENERGIZED. CONTRACTOR NEEDS TO AMEND METERS ON THE APPLICATION AS EXPLAINED.
 
(5) 08/09/2017 08/09/2017 FWE J (1) (0) Y
INSPECTION COMMENTS: METERS ARE READY TO BE SET.OK FOR CON ED TO SET METERS. REINSPECTION BY BEC REQUIRES. NPI
 
(6) 08/29/2017 08/30/2017 DNM C (38) (0) Y
INSPECTION COMMENTS: JOB PASS.

OBJECTION FOR APPLICATION #: B429010
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) DISCONNECTS NOT INDENTIFIED. ART. 230.2(E)
RSLV 07/13/2017 07/13/2017 07/31/2017
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) ALL ELECTRICAL EQUIPMENT NOT IDENTIFIED. ART. 110.22(A)
RSLV 07/13/2017 07/13/2017 07/31/2017
 
003 (255) NO FUSE COORDINATION EXISTS
(BASEMENT) INCREASE IN AMP FOR NEW METERS. AMEND. 240.12(A)
RSLV 07/13/2017 07/13/2017 07/31/2017
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) NO DIRECTORY FOR HOUSE PANELS. ART. 408.4
RSLV 07/13/2017 07/13/2017 07/31/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order