Electrical Application Details for App #: B426485
Premises: 4015 ATLANTIC AVENUE BROOKLYN BIN: 3189293     Block: 7028   Lot: 43
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 4015 ATLANTIC AV Census Tract:   336 Health Area:  9010
ALL FLOORS Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11224 Community Board:   313
Special Place Name:   SEAGATE
Related Job Number:    321177285
DOB Cross Street(s):   BEACH 40 STREET,    BEACH 42 STREET
Status:   C - JOB IS SIGNED OFF 06/19/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/01/2017 6:45 AM
Application Entered:   04/01/2017 Job Start Date:   04/01/2017
Last Change:   06/19/2018 Job End Date:   04/01/2018
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     06/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011756 Licensee Name: LEONID SIMKIN
Firm: 003366 Firm Name: LENS ELECTRIC, INC
Firm Phone: 646-522-7311  Firm Address: 2802 AVENUE Y BROOKLYN NY 11235 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $366.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL APTERMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
OSP        28         
001    24  40    20  24         
002    30  30    16  30         
003    26  28    15  26         
Buildings Total 89  107    57  89     35           
Total Units : 377 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 5 - Removed Meters 6 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/01/2017 Notice: 1 - FIRST NOTICE 05/09/2018
Power Issued: 04/01/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B426485
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/25/2018 04/26/2018 DIT N (18) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO SHOW
 
(2) 05/08/2018 05/09/2018 DIT V (64) (7)
INSPECTION COMMENTS: CORRECT OBJECTIONS
 
(3) 06/04/2018 06/04/2018 DIT C R (39) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B426485
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 001) AFCI NOT PROVIDED FOR SMOKE / CARBON DET. ART 210.12B
RSLV 05/08/2018 05/08/2018 06/04/2018
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 001) LIVING/DINING AREA NOT AFCI PROTECTED . ART 210.12B
RSLV 05/08/2018 05/08/2018 06/04/2018
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 002)AFCI NOT PROVIDED FOR LAUNDRY ROOM, HALLWAY AND SMOKE DET ART210.12B
RSLV 05/08/2018 05/08/2018 06/04/2018
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 003)DEFECTIVE WIRING IN BATHROOM SWITCH & RECEPTACLES. ART 110.2 A
RSLV 05/08/2018 05/08/2018 06/04/2018
 
005 (999) OTHER
(GROUND FLOOR)HVAC UNITS FOR SECOND AND THIRD FLOOR FEEDER CONDUCTOR UNDERSIZED .ART 430.21
RSLV 05/08/2018 05/08/2018 06/04/2018
 
006 (999) OTHER
(GROUND FLOOR) EGC FOR HVAC UNDERSIZED AS PER ART 250.122
RSLV 05/08/2018 05/08/2018 06/04/2018
 
007 (999) OTHER
(GROUND FLOOR) HVAC UNITS NOT PROPERLY IDENTIFIED /LABEL .
RSLV 05/08/2018 05/08/2018 06/04/2018