BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B426438
Premises: 323 EAST 19 STREET BROOKLYN BIN: 3425399     Block: 5162   Lot: 65
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 323 E 19 Census Tract:   514 Health Area:  7210
ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
Related Job Number:    321080511
DOB Cross Street(s):   CORTELYOU ROAD,    DORCHESTER ROAD
Status:   C - JOB IS SIGNED OFF 06/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/31/2017 10:21 AM
Application Entered:   03/31/2017 Job Start Date:   04/01/2017
Last Change:   06/20/2018 Job End Date:   04/01/2018
Appointment Status:   
Last Inspection By:   DAMISO COOTE       On     04/18/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012475 Licensee Name: YEHOSHUA H GREENFELD
Firm: 004283 Firm Name: GREEN STAR ELECTL CONT IN
Firm Phone: 718-643-1500  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,695.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PARK DITMAS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  4  2 600 AMP , 2 400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  2 SETS 600 , 2 SETS 400
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  38  #2/3 BX
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1 SET 500 MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    25  10    25  15         
001    25  50    10  25         
002    35  70    20  35         
003    35  70    20  35         
004    35  70    20  35         
005    35  70    20  35         
006    35  70    20  35         
007    35  60    20  35         
ROF                 
Buildings Total 263  473    137  263     36           
Total Units : 1172 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 39 - Removed Meters 0 = Total Meters 39

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/31/2017 Notice: 1 - FIRST NOTICE 04/12/2018
Power Issued: 03/31/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B426438
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/12/2018 04/12/2018 DAH V (140) (3)
INSPECTION COMMENTS: DEFECTIVE WIRING ARE IN PLACED
 
(2) 04/18/2018 04/19/2018 DIT C R (42) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: B426438
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) KITCHEN DEVICES SETBACK ARE NOT AS PER ARTL . 314 . 20
RSLV 04/12/2018 04/12/2018 04/18/2018
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) COMBO ( 400 A ) SVC PNL NEUTRAL NOT BONDED
RSLV 04/12/2018 04/12/2018 04/18/2018
 
003 (999) OTHER
(BASEMENT) SVC SW ISN'T PROVIDED FOR 40 HP CONTROLLER ARTL 230 . 91
RSLV 04/12/2018 04/12/2018 04/18/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back