BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B425967
Premises: 200 LINDEN BOULEVARD BROOKLYN BIN: 3428516     Block: 5088   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 204 LINDEN BLVD Census Tract:   820 Health Area:  5400
ENTIER Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11226 Community Board:   317
Related Job Number:    321081306
DOB Cross Street(s):   ROGERS AVENUE,    NOSTRAND AVENUE
Status:   C - JOB IS SIGNED OFF 11/20/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/22/2017 4:58 PM
Application Entered:   03/22/2017 Job Start Date:   03/22/2017
Last Change:   11/20/2019 Job End Date:   03/22/2018
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     10/30/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012634 Licensee Name: MOISHE C KLEIN
Firm: 003748 Firm Name: CONTACT ELECTRIC CORP
Firm Phone: 718-438-4225  Firm Address: 1266 36TH STREET BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  321081306
Building Used As:   Z - Commercial/Residential (6  Stores, 69 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BARRY FARKAS
Owner Business Name: LINDEN COURTYARD LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  5  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  69  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  8  
D. Over 250 MCM  12  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  69  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    23    13  45  10  50         
001    95    45  60             
002    100    55  100             
003    100    55  100             
004    100    55  100             
005    100    55  100             
006    100    55  100             
007    85    50  85             
008    85    50  85             
ROF      10  70  120         
Buildings Total 27  793    435  785     170           
Total Units : 2210 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 69 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/22/2017 Notice: 1 - FIRST NOTICE 10/16/2019
Power Issued: 03/22/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B425967
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/16/2019 10/16/2019 CJH V (140) (2)
INSPECTION COMMENTS: NOT A FINAL INSPECTION, RE-INSPECT ENTIRE JOB.
 
(2) 10/25/2019 10/25/2019 CJH N (28) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 10/30/2019 10/30/2019 DAH C R (14) (0)
INSPECTION COMMENTS: THE VIOLATIONS ARE RESOLVED .

OBJECTION FOR APPLICATION #: B425967
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) CELLAR SVC ROOM SVC SWITCHES NOT PROPERLY LABEL 230.2
RSLV 10/16/2019 10/16/2019 10/30/2019
 
002 (999) OTHER
(CELLAR) CELLAR PROPER SIGNAGE NOT PROVIDED FOR SVC ROOM 225.37
RSLV 10/16/2019 10/16/2019 10/30/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.