BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B425651
Premises: 152 GRAND STREET BROOKLYN BIN: 3413905     Block: 2392   Lot: 18
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 152 GRAND ST Census Tract:   551 Health Area:  0400
GRANDSTREET/CELLAR Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11249 Community Board:   301
DOB Cross Street(s):   BERRY STREET,    BEDFORD AVENUE
Status:   C - JOB IS SIGNED OFF 11/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/17/2017 12:13 PM
Application Entered:   03/17/2017 Job Start Date:   03/17/2017
Last Change:   11/04/2017 Job End Date:   03/17/2018
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     09/09/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012361 Licensee Name: ANGELO DOMINGUEZ
Firm: 004263 Firm Name: ALLTECH ELECL CONTNG CORP
Firm Phone: 646-491-2088  Firm Address: 227 SEA BREEZE AVE., STE 201 BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   CLOTHING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHAI LLUZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1 SET OF 3 PHASE 500 MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/17/2017 Notice: 1 - FIRST NOTICE 08/09/2017
Power Issued: 03/17/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE ARE INSTALLING A NEW 400 AMP THREE PHASE SERVICE WITH A THREE PHASE MAIN BREAKER 42 CIRCUIT THREE PHASE PANEL AND METER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B425651
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2017 07/13/2017 CZH N (35) (0) Y
INSPECTION COMMENTS: NO ACCESS, CONTRACTOR WAS CALLED.
 
(2) 08/09/2017 08/09/2017 FDY V (31) (4)
INSPECTION COMMENTS: OBJECTIONS ARE ISSUED TO THIS JOB. A NEW PANEL ON A SEPARATE APPLICATION IS INSTALLED TO THE SERVICE. THAT JOB IS IN PROGRESS.
 
(3) 09/09/2017 09/11/2017 DNM C R (25) (0)
INSPECTION COMMENTS: AT TIME OF INSPECTION ELECTRICIAN WAS CORRECTING OBJECTIONS, JOB PASS.

OBJECTION FOR APPLICATION #: B425651
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) 250.52(A)(1) THE WATER METER IS NOT BONDED WITH A JUMPER.
RSLV 08/09/2017 08/09/2017 09/09/2017
 
002 (999) OTHER
(CELLAR) 110.26(D) ILLUMINATION NEEDED FOR THE SERVICE.
RSLV 08/09/2017 08/09/2017 09/09/2017
 
003 (999) OTHER
(CELLAR)250.28(C),(D) A MAIN BONDING JUMPER CONNECTION IS NEEDED AT THESERVICE.
RSLV 08/09/2017 08/09/2017 09/09/2017
 
004 (999) OTHER
(CELLAR)250.102(C) THE BONDING JUMPERS ON THE SUPPLY SIDE OF THE SERVICE ARENOT SIZED PROPERLY. 1/0 IS NEEDED AS A MINIMUM.
RSLV 08/09/2017 08/09/2017 09/09/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order